Vapour compression refrigeration

Vapour compression refrigeration: cycle, COP, P–h/T–s diagrams, superheat/subcool effects, real vs ideal, sizing (mass flow, power) and common exam numericals.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Refrigerators, air-conditioners, heat pumps and many industrial chillers use vapour compression refrigeration (VCR). Understanding the cycle lets you compute COP, size compressors and heat exchangers, diagnose inefficiencies, and answer core interview and GATE ME problems confidently.

Key ideas

  • A refrigerator is a heat engine run in reverse: it moves heat from a low-temperature space (evaporator) to a high-temperature sink (condenser) using work input to the compressor.
  • Vapour compression refrigeration (VCR) cycle (basic/ideal): four steady-flow components connected in a loop, usually labeled 1→2→3→4→1 on P–h or T–s diagrams.
    • 1→2: Compression (ideally isentropic) of low-pressure refrigerant vapour to high pressure. Work input increases enthalpy and temperature.
    • 2→3: Condensation at almost constant pressure: superheated vapour first desuperheats and then condenses to liquid, rejecting heat to surroundings.
    • 3→4: Expansion (throttling) through an expansion valve/capillary (isoenthalpic): pressure and temperature drop, some liquid flashes to vapour; entropy increases.
    • 4→1: Evaporation at almost constant pressure: liquid–vapour mixture absorbs heat from the refrigerated space until it becomes saturated or slightly superheated vapour at compressor inlet.
  • Sign convention used here: heat absorbed in evaporator Q̇_L is positive, heat rejected at condenser Q̇_H is positive, compressor work input Ẇ is positive. Steady state, negligible kinetic/potential energy changes unless stated.
  • Coefficient of performance (refrigerator): COP_R = desired effect/work input = Q̇_L/Ẇ. For the idealized VCR without pressure drops: COP_R = (h1 − h4)/(h2 − h1).
  • First Law (steady-flow energy balances) for each component (neglecting ΔKE, ΔPE):
    • Compressor: Ẇ_comp = ṁ(h2 − h1) if adiabatic.
    • Condenser: Q̇_H = ṁ(h2 − h3).
    • Expansion valve: h3 = h4, Ẇ ≈ 0, Q̇ ≈ 0.
    • Evaporator: Q̇_L = ṁ(h1 − h4).
    • Overall cycle: Ẇ_net = Q̇_H − Q̇_L = ṁ[(h2 − h3) − (h1 − h4)]. With a throttling device (h3 = h4), Ẇ_net = ṁ(h2 − h1).
  • Second Law statements (for refrigerators/heat pumps):
    • Clausius statement implies work is needed to transfer heat from cold to hot.
    • Reversible refrigerator (Carnot) between T_L and T_H has COP_Carnot = T_L/(T_H − T_L) (temperatures in K). Any real VCR has COP < COP_Carnot.
  • Isentropic (adiabatic, reversible) compression: ideal model for state 1→2s with s2s = s1. Real compressors deviate: define compressor isentropic efficiency η_is,c = (h2s − h1)/(h2 − h1) < 1.
  • Why throttling instead of an expander? Throttling is simple, cheap and reliable; it is irreversibility-heavy (s increases, no work recovery). Replacing with an expander can improve COP but adds cost/complexity; rarely used in comfort cooling.
  • Dry vs wet compression:
    • Dry (or “dry saturated”/slightly superheated) suction is desired: x1 ≈ 1 at compressor inlet to avoid liquid droplets that can damage the compressor.
    • Wet compression (x1 < 1) is unsafe and reduces compressor life and efficiency.
  • Superheating and subcooling:
    • Suction superheat (state 1 above saturation at evaporator pressure) ensures dry compression and can slightly increase Q̇_L; it also increases compressor work. Net effect on COP depends on refrigerant and conditions.
    • Liquid subcooling (state 3 below saturation at condenser pressure) raises the refrigerating effect (h1 − h4 increases because h4 = h3 decreases) and typically improves COP.
    • A liquid–suction heat exchanger (LSHX) trades some suction superheat for liquid subcooling; often increases COP for refrigerants with significant throttling losses (large positive Joule–Thomson coefficient). May not help for all refrigerants.
  • Effect of operating temperatures:
    • Lower evaporator temperature (at fixed condenser T) lowers COP because the compressor work increases and refrigerating effect may change modestly.
    • Higher condenser temperature (at fixed evaporator T) lowers COP because discharge enthalpy rises.
    • Practical design balances approach temperatures (LMTD) in heat exchangers with energy use.
  • Real-device departures from ideal:
    • Non-isentropic compression (η_is,c < 1) increases Ẇ.
    • Pressure drops in evaporator/condenser and connecting lines reduce effective T_e and raise effective T_c.
    • Nonzero superheat/subcool are common due to control strategy (e.g., thermostatic/ electronic expansion valve maintains superheat).
    • Motor/compressor mechanical losses: define shaft power vs electrical power using efficiencies.
  • Performance quantities:
    • Refrigerating effect (per kg): q_L = h1 − h4 (kJ/kg).
    • Specific compressor work: w_comp = h2 − h1 (kJ/kg).
    • Heat rejected (per kg): q_H = h2 − h3 (kJ/kg).
    • Mass flow rate: ṁ = Q̇_L/q_L (kg/s).
    • 1 ton of refrigeration (TR): 1 TR = 3.517 kW of cooling capacity (by definition; equivalent to 211 kJ/min).
  • Diagrams and how to read them:
    • P–h diagram is very useful to read enthalpy differences: vertical moves indicate isoenthalpic throttling (h constant), horizontal moves indicate (nearly) isobaric heat exchange (P ≈ const). There is no direct area interpretation for heat/work on a P–h diagram.
    • T–s diagram shows that compression is vertical (ideal isentropic), condenser/evaporator segments are nearly horizontal—indeed isothermal for pure refrigerants with negligible pressure drop—while zeotropic blends show temperature glide; throttling moves right (entropy increase) at roughly constant h.
  • Refrigerant selection (brief): Safety, compatibility, efficiency, environmental metrics (ODP ≈ 0 mandated, low GWP preferred), operating pressures matching component ratings, availability and cost. Common: R-134a, R-22 (legacy), R-410A, R-404A (commercial), R-290 (propane), R-600a (domestic), R-32, and ammonia (R-717) in industrial systems.
  • Controls/expansion devices:
    • Capillary tube: simple, fixed; sensitive to charge and load.
    • Thermostatic expansion valve (TXV)/EEV: modulates to maintain target superheat; improves stability and efficiency.
  • Extensions (outline only): Two-stage compression with intercooling and an economizer reduces work and improves COP at low evaporator temperatures. Oil cooling and liquid injection strategies manage discharge temperatures.

Formulas

  • COP_R = Q̇_L / Ẇ — COP of refrigerator; Q̇_L: cooling capacity (W), Ẇ: compressor input power (W); steady operation.
  • COP_R = (h1 − h4) / (h2 − h1) — For VCR with states 1 (compressor inlet), 2 (compressor exit), 3 (condenser exit), 4 (evaporator inlet) and negligible pressure drops; h in kJ/kg.
  • COP_HP = Q̇_H / Ẇ = 1 + COP_R — Heat pump COP; Q̇_H: heat rejected (W).
  • Q̇_L = ṁ · (h1 − h4) — Evaporator heat absorbed; ṁ in kg/s; h in kJ/kg; result W.
  • Q̇_H = ṁ · (h2 − h3) — Condenser heat rejected; same units as above.
  • Ẇ_comp = ṁ · (h2 − h1) — Thermodynamic compressor power imparted to the refrigerant for an adiabatic compressor (ignoring mechanical losses); W. Shaft and electrical: Ẇ_shaft = Ẇ_comp/η_mech, Ẇ_elec = Ẇ_shaft/η_motor = Ẇ_comp/(η_mech·η_motor).
  • η_is,c = (h2s − h1) / (h2 − h1) — Compressor isentropic efficiency; h2s: discharge enthalpy for isentropic compression (kJ/kg).
  • h3 = h4 — Throttling (expansion valve/capillary) is isoenthalpic; valid for adiabatic, negligible shaft work.
  • x4 ≈ (h4 − h_f,evap) / h_fg,evap — Quality at evaporator inlet after throttling; h_f,evap and h_fg,evap from refrigerant tables at evaporator pressure; dimensionless; approximation assumes two-phase at entry.
  • ṁ = Q̇_L / q_L — Mass flow rate; q_L = h1 − h4 (kJ/kg); yields kg/s when Q̇_L in W and q_L in kJ/kg (note 1 kW = 1 kJ/s).
  • V̇_suction = ṁ · v1 — Volumetric flow rate at compressor suction; v1: specific volume at state 1 (m³/kg); result m³/s.
  • V̇_swept = V̇_suction / η_v — Required compressor swept volume rate; η_v: volumetric efficiency (dimensionless); applicable to positive-displacement compressors.
  • COP_Carnot = T_L / (T_H − T_L) — Ideal reversible refrigerator COP between heat-source at T_L and heat-sink at T_H; T in K; upper bound.
  • COP_HP,Carnot = T_H / (T_H − T_L) — Ideal reversible heat pump COP; T in K.
  • Δq_L|subcool ≈ c_p,liq · ΔT_sub — Increase in refrigerating effect per kg due to ΔT_sub of liquid; c_p,liq in kJ/(kg·K); approximation assuming constant c_p and no pressure drop.
  • Δq_L|superheat ≈ c_p,vap · ΔT_sh — Increase in refrigerating effect per kg due to suction superheat; c_p,vap in kJ/(kg·K); compressor work also rises; approximation.
  • 1 TR = 3.517 kW — Ton of refrigeration to SI conversion.

Worked examples

Example 1 — Direct cycle performance from given enthalpies Given: A VCR operates with the following states (kJ/kg): h1 = 392 (compressor inlet), h2 = 430 (compressor exit), h3 = 251 (condenser exit, saturated liquid), h4 = 251 (after expansion, since h3 = h4). The required cooling capacity is Q̇_L = 10 kW. Assume steady state, negligible pressure drops, adiabatic compressor, no mechanical/electrical losses in this calculation.

Find: (a) COP, (b) mass flow rate, (c) compressor power, (d) heat rejected at condenser.

Steps:

  1. Refrigerating effect per kg: q_L = h1 − h4 = 392 − 251 = 141 kJ/kg.
  2. Compressor work per kg: w_comp = h2 − h1 = 430 − 392 = 38 kJ/kg.
  3. COP using COP_R = q_L / w_comp: COP_R = 141 / 38 = 3.7105 → ≈ 3.71 (dimensionless).
  4. Mass flow using ṁ = Q̇_L / q_L: ṁ = 10 kJ/s ÷ 141 kJ/kg = 0.07092 kg/s.
  5. Compressor power using Ẇ_comp = ṁ · (h2 − h1): Ẇ_comp = 0.07092 kg/s · 38 kJ/kg = 2.6949 kJ/s = 2.695 kW.
  6. Condenser heat rejection using Q̇_H = ṁ · (h2 − h3): Q̇_H = 0.07092 kg/s · (430 − 251) kJ/kg = 0.07092 · 179 = 12.695 kJ/s = 12.695 kW.

Answer: (a) COP ≈ 3.71; (b) ṁ = 0.0709 kg/s; (c) Ẇ_comp = 2.70 kW (rounded); (d) Q̇_H ≈ 12.70 kW.

Example 2 — GATE-level: superheat, subcool, isentropic efficiency, swept volume Given: A single-stage VCR using a refrigerant operates between an evaporator saturation temperature near −5 °C and a condenser near 40 °C. At the compressor inlet, the vapour is 5 K superheated. At the condenser exit, the liquid is 3 K subcooled. Data (per kg of refrigerant, provided):

  • h1 = 400 kJ/kg and v1 = 0.080 m³/kg at compressor inlet (includes 5 K superheat).
  • Isentropic discharge enthalpy h2s = 430 kJ/kg at compressor exit pressure.
  • Compressor isentropic efficiency η_is,c = 0.80.
  • Condenser exit enthalpy after 3 K subcooling: h3 = 246 kJ/kg.
  • Throttling is isoenthalpic: h4 = h3. Cooling capacity required: 5 TR. Volumetric efficiency of the reciprocating compressor: η_v = 0.75. Assume adiabatic compressor, negligible pressure drops in heat exchangers, and neglect mechanical/motor losses for power calculation.

Find: (a) actual compressor discharge enthalpy h2, (b) COP, (c) mass flow rate, (d) compressor power, (e) condenser heat rejection, (f) required swept volume rate.

Steps:

  1. Actual discharge enthalpy using compressor isentropic efficiency: Formula: η_is,c = (h2s − h1) / (h2 − h1) ⇒ h2 = h1 + (h2s − h1)/η_is,c. Numbers: h2 = 400 + (430 − 400)/0.80 = 400 + 30/0.80 = 400 + 37.5 = 437.5 kJ/kg.
  2. Refrigerating effect per kg: q_L = h1 − h4 = 400 − 246 = 154 kJ/kg.
  3. Specific compressor work (actual): w_comp = h2 − h1 = 437.5 − 400 = 37.5 kJ/kg.
  4. COP using COP_R = q_L / w_comp: COP_R = 154 / 37.5 = 4.1067 → ≈ 4.11.
  5. Convert capacity: 5 TR to kW using 1 TR = 3.517 kW: Q̇_L = 5 × 3.517 = 17.585 kW.
  6. Mass flow using ṁ = Q̇_L / q_L: ṁ = 17.585 kJ/s ÷ 154 kJ/kg = 0.1142 kg/s.
  7. Compressor power using Ẇ_comp = ṁ · w_comp: Ẇ_comp = 0.1142 kg/s · 37.5 kJ/kg = 4.2825 kJ/s = 4.283 kW.
  8. Condenser heat rejection using Q̇_H = ṁ · (h2 − h3): Q̇_H = 0.1142 · (437.5 − 246) = 0.1142 · 191.5 = 21.88 kW. Check: Q̇_H ≈ Q̇_L + Ẇ_comp = 17.585 + 4.283 = 21.868 kW (consistent by rounding).
  9. Suction volumetric flow using V̇_suction = ṁ · v1: V̇_suction = 0.1142 kg/s · 0.080 m³/kg = 0.00914 m³/s.
  10. Required swept volume rate using V̇_swept = V̇_suction / η_v: V̇_swept = 0.00914 / 0.75 = 0.01219 m³/s = 0.731 m³/min.

Answer: (a) h2 = 437.5 kJ/kg; (b) COP ≈ 4.11; (c) ṁ ≈ 0.114 kg/s; (d) Ẇ_comp ≈ 4.28 kW; (e) Q̇_H ≈ 21.9 kW; (f) V̇_swept ≈ 0.0122 m³/s (≈ 0.731 m³/min).

Common mistakes

  • Forgetting that throttling is isoenthalpic (h3 = h4), or using saturated-liquid h3 without accounting for subcooling.
  • Using saturation properties at the wrong pressure/temperature, or mixing states across different refrigerants.
  • Ignoring superheat maintained by the expansion valve and assuming state 1 is exactly dry saturated when data state otherwise.
  • Treating compressor isentropic efficiency as η = (h2 − h1)/(h2s − h1) (that is turbine convention); for compressors it is inverted.
  • Forgetting to convert TR to kW (1 TR = 3.517 kW) or mixing kJ/kg with kW directly without time basis.
  • Neglecting pressure drops in lines/heat exchangers when a problem explicitly provides them; this shifts state points and changes h values.
  • Assuming subcooling always dramatically improves COP; its benefit depends on refrigerant and how compressor work changes due to suction superheat.
  • Calculating volumetric displacement without dividing by volumetric efficiency (η_v), leading to undersized compressors.
  • Skipping a consistency check: Q̇_H should equal Q̇_L + Ẇ_comp (within rounding).

For GATE ME

  • Direct P–h based numericals: given state enthalpies or saturation data, compute COP, mass flow rate, compressor power, and heat rejected.
  • Conceptual questions on T–s/P–h diagrams: identify which processes are isentropic/isobaric/isoenthalpic and the effect of throttling on entropy.
  • Variations with superheat and subcool: evaluate changes in refrigerating effect, compressor work, and COP.
  • Isentropic efficiency of compressor: compute actual discharge enthalpy from h2s and η_is,c, and recalc performance.
  • Capacity sizing: given TR and state enthalpies, find ṁ, Ẇ, and sometimes suction volumetric flow and swept volume using η_v.
  • Comparative COP questions: relative trends with evaporator/condenser temperatures and comparison to Carnot COP (and Carnot heat pump COP).
  • Realistic cycle with pressure drops: adjust state pressures and use correct property data; recompute q_L, w_comp. Practice: drawing P–h with labelled states and writing balances; quick TR↔kW conversions; manipulating η_is,c relations; keeping units straight (kW vs kJ/kg); and consistency checks.

Quick check

  1. In an ideal VCR (dry saturated at compressor inlet, saturated liquid at condenser exit), which property is constant across the expansion valve? And what happens to entropy?
  2. State whether increasing condenser temperature (everything else same) increases or decreases COP, and why.
  3. A 3 TR VCR has q_L = 140 kJ/kg and w_comp = 40 kJ/kg. Find COP and mass flow rate.

Answers: 1) Enthalpy is constant (h3 = h4); entropy increases due to throttling irreversibility. 2) COP decreases because compressor work rises and the discharge enthalpy increases while q_L typically changes less. 3) COP = 140/40 = 3.5; Q̇_L = 3×3.517 = 10.551 kW, so ṁ = 10.551/140 = 0.0754 kg/s.