Vapour absorption refrigeration and heat pumps

Principles, components, performance and COP relations of vapour absorption refrigeration and absorption heat pumps, with ideal bounds, mass/energy balances, and exam-focused formulas and examples.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Vapour absorption refrigeration and absorption heat pumps can use low-grade or waste heat (solar, engine exhaust, steam condensate) to provide cooling or heating with minimal electricity. They have few moving parts, low noise, and suit industrial process integration and district cooling/heating common in power and process plants.

Key ideas

  • Vapour Absorption Refrigeration System (VARS): A refrigeration system in which the mechanical compressor of a vapour compression cycle is replaced by a thermochemical loop that uses a refrigerant–absorbent pair (e.g., NH₃–H₂O or H₂O–LiBr). Heat input to a generator drives refrigerant desorption instead of mechanical work input.
  • Refrigerant: The working fluid that evaporates at low temperature to absorb heat (cooling effect) and condenses at higher temperature to reject heat. Examples: ammonia (in NH₃–H₂O), water (in H₂O–LiBr).
  • Absorbent: The second component that has strong affinity for the refrigerant and absorbs its vapour in the absorber, releasing heat. Examples: water (for NH₃), lithium bromide (for H₂O).
  • Strong/Rich solution: The absorbent solution with higher mass fraction of refrigerant (e.g., high NH₃ in water). Denote its refrigerant mass fraction as x_r.
  • Weak/Lean solution: The absorbent solution with lower mass fraction of refrigerant after desorption in the generator. Denote its refrigerant mass fraction as x_w (x_w < x_r).
  • Main components and roles (steady state, negligible kinetic/potential changes):
    • Evaporator: Low pressure; refrigerant absorbs heat Q_L from the cooled space/fluid and evaporates.
    • Absorber: Low pressure; refrigerant vapour is absorbed into the absorbent, releasing heat Q_abs to surroundings (must be removed by cooling water/air).
    • Solution pump: Raises pressure of liquid strong solution from evaporator/absorber pressure to generator/condenser pressure. Work W_p is usually very small.
    • Generator (Desorber): High pressure; heat input Q_H drives off refrigerant vapour from the strong solution, producing weak solution.
    • Rectifier/Analyzer (mainly for NH₃–H₂O): Cleans refrigerant vapour by condensing/returning carried-over absorbent (water), improving refrigerant purity.
    • Condenser: High pressure; refrigerant vapour rejects heat Q_c and condenses to liquid.
    • Expansion devices: Throttling valves reduce pressure of the condensed refrigerant and of the weak solution returning to absorber.
    • Solution heat exchanger (SHX): Recovers heat by exchanging between hot weak solution (from generator) and cold strong solution (to generator), reducing required Q_H and improving COP.
  • Absorption Heat Pump (AHP): Same loop operated with heating as the objective. The useful heat output is typically the sum of absorber and condenser heat rejections (both at near the same sink temperature), powered mainly by heat to the generator.
  • Sign conventions used in these notes:
    • Heat added to a control volume is positive (Q > 0); heat rejected is negative in that CV but reported here by magnitude (Q_abs, Q_c) as positive rates.
    • Work input to pump W_p > 0 (to the system). For the whole machine, W_p is small relative to heat rates.
  • Performance metrics:
    • Coefficient of Performance of absorption refrigerator (COP_R,abs): Useful refrigeration effect per required input energy. Exact definition uses both generator heat and pump work; often W_p is negligible.
    • Coefficient of Performance of absorption heat pump (COP_HP,abs): Useful heating delivered (usually absorber + condenser) per required input energy.
  • First-law balance of the whole absorption machine (steady state): Q_H + W_p + Q_L = Q_c + Q_abs. This identity underlies many quick checks: total heat rejected equals the sum of all inputs (heat and negligible work).
  • Second-law bounds (Carnot reasoning):
    • Carnot’s theorem (exact statement): “No heat engine operating between two thermal reservoirs can be more efficient than a reversible (Carnot) engine operating between the same reservoirs.” For refrigerators/heat pumps, the corresponding reversible COPs provide upper bounds when operating between two fixed-temperature reservoirs.
    • Idealized upper bound for a heat-driven absorption refrigerator (useful for estimates): Model the system as a reversible heat engine between T_H (generator) and T_0 (absorber/condenser) that drives a reversible refrigerator between T_0 and T_e (evaporator). Then COP_abs,max ≈ COP_Carnot,ref × η_Carnot,HE.
    • This upper bound is optimistic because real VARS has additional irreversibilities (solution mixing/separation, finite ΔT in heat exchangers, non-ideal rectification, pressure drops).
  • Working pairs: Selection considerations include affinity, volatility mismatch (so refrigerant can be vaporised and absorbent remain mostly liquid), chemical stability, corrosion, safety, and operating temperature range.
    • NH₃–H₂O: Refrigerant = ammonia; absorbent = water. Suitable for sub-zero refrigeration (ammonia remains volatile). Requires rectification to limit water carryover; ammonia is toxic and mildly flammable.
    • H₂O–LiBr: Refrigerant = water; absorbent = lithium bromide. Suitable for air-conditioning above 0 °C (water refrigerant freezes near 0 °C), operates under deep vacuum; risk of crystallisation at high LiBr concentration and low absorber temperature; generally non-toxic but needs tightness to avoid air ingress.
  • Why real devices differ from ideal:
    • Finite temperature differences in generator, absorber, condenser, and evaporator (approach temperatures) cause entropy generation.
    • Incomplete rectification/analyzing (especially NH₃–H₂O) reduces effective driving potentials.
    • Pressure drops and solution pumping losses (small but nonzero).
    • Heat leaks, non-condensable gases (need purging), and solution heat exchanger effectiveness < 1.
  • Standard results and useful relations:
    • Pump work is typically ≤1–2% of Q_H in single-effect systems (negligible for many calculations; verify case-by-case).
    • Adding a solution heat exchanger increases COP by reducing required Q_H for the same Q_L.
    • For heating duty using the same machine, exact identity: COP_HP,abs = 1 + COP_R,abs when COP_R,abs is defined with (Q_H + W_p) in the denominator. If, additionally, W_p is neglected and you use COP_R,abs ≈ Q_L/Q_H, then COP_HP,abs ≈ 1 + Q_L/Q_H.
    • Typical single-effect COP ranges (very system-dependent): ~0.6–0.8 for H₂O–LiBr chillers; ~0.2–0.6 for NH₃–H₂O refrigerators. Multi-effect systems can be higher but need higher T_H.
  • Mass balances (NH₃–H₂O, assuming pure NH₃ refrigerant from generator):
    • Total balance at generator: m_s (rich) = m_w (weak) + m_r (refrigerant vapour).
    • Component (NH₃) balance: m_s x_r = m_w x_w + m_r (NH₃ mass fraction in vapour ≈ 1).
    • From these, define the solution circulation ratio f ≡ m_s/m_r = (1 − x_w)/(x_r − x_w). Lower f implies less solution flow and usually lower Q_H.
  • Heat pumps in absorption context:
    • Type commonly used for building heating: generator at moderate/high T_H (e.g., steam), absorber and condenser reject heat at heating supply temperature. The useful heating is Q_abs + Q_c.
    • An absorption “heat transformer” (advanced) can upgrade heat to a temperature above T_H with different configurations; outside the scope of most introductory exams.

Formulas

COP_R,abs = Q_L / (Q_H + W_p)

  • Coefficient of performance of absorption refrigerator; Q_L (W) is evaporator load; Q_H (W) is generator heat input; W_p (W) is pump work input. Exact definition; steady state.

COP_R,abs ≈ Q_L / Q_H

  • Approximate COP of absorption refrigerator when pump work is negligible (<~2%).

COP_HP,abs = (Q_c + Q_abs) / (Q_H + W_p)

  • Heating COP for absorption heat pump; useful heat is sum of condenser and absorber heat rejections (W). Exact; steady state.

COP_HP,abs = 1 + COP_R,abs

  • Exact identity when COP_R,abs is defined with the same denominator (Q_H + W_p): since Q_c + Q_abs = Q_H + W_p + Q_L.

COP_HP,abs ≈ 1 + Q_L / Q_H

  • Using the negligible-pump-work approximation for both COPs.

Q_H + W_p + Q_L − Q_c − Q_abs = 0

  • First-law balance for the entire absorption system at steady state; all terms in watts; sign convention: heat to the system positive.

COP_R,Carnot = T_L / (T_H − T_L)

  • Reversible (Carnot) refrigerator COP between cold reservoir at T_L (K) and hot reservoir at T_H (K), with T_H > T_L; applies to any reversible refrigerator between two reservoirs.

COP_HP,Carnot = T_H / (T_H − T_L)

  • Reversible (Carnot) heat pump COP between hot reservoir at T_H (K) and cold reservoir at T_L (K), T_H > T_L.

COP_abs,max ≈ (T_e / (T_0 − T_e)) × (1 − T_0 / T_H)

  • Idealized upper bound for a heat-driven absorption refrigerator modeled as a reversible heat engine (between T_H and T_0) driving a reversible refrigerator (between T_0 and T_e). T_e (K): evaporator temperature; T_0 (K): absorber/condenser temperature; T_H (K): generator heat-source temperature; assumes negligible internal temperature drops and perfect rectification.

f = m_s / m_r = (1 − x_w) / (x_r − x_w)

  • Solution circulation ratio for NH₃–H₂O with pure NH₃ as refrigerant; m_s (kg/s) rich solution to generator; m_r (kg/s) refrigerant mass flow; x_r, x_w are NH₃ mass fractions (dimensionless) in rich and weak solutions, respectively. Steady state; negligible water in refrigerant vapour.

w_p ≈ v_s · (p_H − p_L)

  • Specific pump work for incompressible solution; w_p (J/kg of solution); v_s (m³/kg) specific volume of solution; p_H, p_L (Pa) are high/low pressures. Often very small.

W_p = m_s · w_p

  • Pump power (W) from specific work and solution mass flow m_s (kg/s).

Q_out = Q_c + Q_abs = Q_H + W_p + Q_L

  • Total heat rejected (W) equals total input; steady state, whole machine.

Worked examples

Example 1 — Direct calculation and interpretation Given: An absorption refrigeration unit requires generator heat input Q_H = 12 kW and delivers cooling Q_L = 8 kW. Neglect pump work and heat leaks.

Steps:

  1. COP of refrigerator: Formula: COP_R,abs ≈ Q_L / Q_H Numbers: = 8 kW / 12 kW = 0.6667 (dimensionless)

  2. Total heat rejected at absorber + condenser: Formula: Q_out = Q_H + Q_L Numbers: = 12 kW + 8 kW = 20 kW

  3. If the same machine is used as a heat pump (useful heat = Q_out), heating COP: Formula: COP_HP,abs ≈ Q_out / Q_H Numbers: = 20 kW / 12 kW = 1.6667 (dimensionless)

Answers:

  • COP_R,abs = 0.667 (dimensionless)
  • Q_out = 20 kW
  • COP_HP,abs = 1.667 (dimensionless)

Assumptions: Steady state; pump work negligible; absorber and condenser reject to the same sink so Q_out sums directly.

Example 2 — GATE-style combined: circulation ratio and ideal vs actual COP A single-effect NH₃–H₂O absorption refrigerator operates with:

  • Evaporator at −10 °C (T_e = 263 K), absorber/condenser at 30 °C (T_0 = 303 K), generator heated by a source at 140 °C (T_H = 413 K).
  • Rich solution NH₃ mass fraction x_r = 0.46; weak solution mass fraction x_w = 0.30.
  • Refrigeration capacity Q_L = 7.0 kW. Neglect pump work and pressure drops. Assume refrigerant vapour from generator is pure NH₃ and rectification is ideal.

Tasks: (a) Compute the solution circulation ratio f. (b) Compute the idealized upper bound COP_abs,max from temperatures. (c) If the actual machine achieves 40% of this bound, determine the required generator heat Q_H and the total heat rejected Q_out.

Steps:

  1. Circulation ratio f: Formula: f = (1 − x_w) / (x_r − x_w) Numbers: = (1 − 0.30) / (0.46 − 0.30) = 0.70 / 0.16 = 4.375 (dimensionless)

  2. Idealized maximum COP (heat-engine × refrigerator model): Formula: COP_abs,max ≈ (T_e / (T_0 − T_e)) × (1 − T_0 / T_H) Numbers:

    • T_0 − T_e = 303 − 263 = 40 K
    • T_e / (T_0 − T_e) = 263 / 40 = 6.575
    • 1 − T_0 / T_H = 1 − (303 / 413) = 1 − 0.73317 = 0.26683
    • Product = 6.575 × 0.26683 = 1.756 (dimensionless)
  3. Actual COP at 40% of the bound: Formula: COP_R,actual = 0.40 × COP_abs,max Numbers: = 0.40 × 1.756 = 0.7024 (dimensionless)

  4. Required generator heat Q_H for Q_L = 7.0 kW: Formula: Q_H = Q_L / COP_R,actual Numbers: = 7.0 kW / 0.7024 = 9.966 kW

  5. Total heat rejected Q_out (absorber + condenser): Formula: Q_out = Q_H + Q_L Numbers: = 9.966 kW + 7.0 kW = 16.966 kW

Answers:

  • f = 4.375 (dimensionless)
  • COP_abs,max = 1.756 (dimensionless)
  • COP_R,actual = 0.702 (dimensionless)
  • Q_H = 9.97 kW
  • Q_out = 16.97 kW

Assumptions: Steady state; negligible pump work; perfect rectification; absorber and condenser at the same T_0; no internal ΔT losses (for the bound only); concentrations apply at generator/absorber appropriately.

Common mistakes

  • Forgetting that the useful heating in an absorption heat pump is Q_abs + Q_c, not just condenser heat.
  • Ignoring the rectifier/analyzer in NH₃–H₂O and assuming perfectly pure refrigerant without stating the assumption.
  • Using Carnot formulas without converting all temperatures to kelvin and without specifying which reservoirs (T_e, T_0, T_H) correspond to which device.
  • Neglecting absorber cooling load when sizing heat rejection (Q_out is often much larger than Q_c alone).
  • Misidentifying strong vs weak solution and hence getting the circulation ratio sign wrong.
  • Assuming pump work is exactly zero; it is small but not identically zero.

For GATE ME

  • Conceptual: Compare VARS vs vapour compression (driving energy, components, where heat/work enter, pros/cons, typical applications). Identify each component’s role (generator, absorber, rectifier, SHX) and the refrigerant/absorbent roles for NH₃–H₂O and H₂O–LiBr.
  • Performance: Compute COP_R,abs from given Q_H and Q_L; compute COP_HP,abs; use the whole-system energy balance to find missing heat rates. Practise the identity COP_HP,abs = 1 + COP_R,abs when definitions are consistent, and know the negligible-pump-work approximation.
  • Ideal limits: Given T_e, T_0, T_H, estimate the idealized upper bound COP_abs,max using the heat-engine × refrigerator model; compare to actual COP and infer an efficiency factor.
  • Mass balances: Derive and use the circulation ratio f = (1 − x_w)/(x_r − x_w) (NH₃–H₂O) and understand how x_r and x_w affect solution flow and generator duty.
  • Practical aspects: Typical COP ranges, why LiBr systems cannot serve sub-zero evaporators, risk of LiBr crystallisation, need for purging non-condensables, effect of adding a solution heat exchanger.
  • Be comfortable stating assumptions, drawing neat block diagrams, and writing clear control-volume balances.

Quick check

  1. In NH₃–H₂O VARS, which has the higher ammonia mass fraction: the strong solution or the weak solution? Why?
  2. An absorption refrigerator has COP_R,abs = 0.60. Approximately what is its heating COP if used as an absorption heat pump, neglecting pump work?
  3. Compute the circulation ratio f for x_r = 0.48 and x_w = 0.34 in NH₃–H₂O.

Answers: 1) Strong (rich) solution; it has higher refrigerant (NH₃) content because absorption in the absorber increases NH₃ fraction. 2) ≈ 1 + 0.60 = 1.60 (dimensionless). 3) f = (1 − 0.34)/(0.48 − 0.34) = 0.66/0.14 = 4.714 (dimensionless).