Psychrometry and air conditioning
Psychrometry and air conditioning — properties of moist air, psychrometric charts, standard air-conditioning processes, coil performance (ADP/BF), comfort and load splits — with formulas and numericals used in design and GATE ME.
Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.
Why it matters
Air conditioning design lives or dies on psychrometrics: knowing how temperature, humidity, and enthalpy of moist air change in real equipment. Getting these right determines comfort, indoor air quality, coil size, and energy use in buildings, vehicles, and industrial drying/conditioning.
Key ideas
Moist air is a mixture of dry air (mostly N2, O2) and water vapour at low partial pressures. At typical HVAC conditions, dry air and water vapour behave as ideal gases, and the mixture follows Dalton’s law: total pressure equals the sum of partial pressures.
Assumptions (standard in HVAC unless stated otherwise): P ≈ 1 atm, ideal-gas behaviour for both components, negligible liquid water carryover unless dehumidifying, steady flow, and properties referenced per kg of dry air.
State variables and measurements
- Dry-bulb temperature (DBT, t_db): ordinary air temperature measured by a standard thermometer.
- Wet-bulb temperature (WBT, t_wb): temperature indicated by a wetted sensor with airflow; reflects combined heat and mass transfer. The thermodynamic wet-bulb temperature equals the adiabatic saturation temperature under ideal conditions; a sling psychrometer approximates this.
- Dew-point temperature (T_dp): temperature at which water vapour in air at a given partial pressure would just saturate (condense begins). Determined by equating the vapour partial pressure to saturation pressure at T_dp.
- Humidity ratio (w) (also called mixing ratio): mass of water vapour per mass of dry air, kg_v/kg_da.
- Specific humidity (SH): mass of water vapour per mass of moist air; SH = w/(1 + w). Many HVAC texts use w; exam questions may ask to distinguish.
- Relative humidity (φ): ratio of actual partial pressure of water vapour to its saturation pressure at t_db, 0–1 (or %).
- Specific enthalpy of moist air (h): enthalpy per kg of dry air, referenced to 0 °C liquid water and 0 °C dry air (common HVAC reference). Approximate linear function of t_db and w.
- Specific volume (v): m³ of moist air per kg of dry air.
Moist air properties from first principles
- Dalton’s law: P = p_a + p_v; dry air and vapour partial pressures add to total.
- Ideal-gas relations apply to each component: p·v = R·T with R_da ≈ 0.287 kJ/(kg·K) for dry air.
- Saturation properties of water (p_ws vs T, h_fg, etc.) come from steam tables; in exams, values are given, or you read from a psychrometric chart.
Psychrometric chart
- A graphical map of moist-air states at fixed pressure (usually 1.013 bar). Axes: horizontal is t_db; vertical is humidity ratio w. Curves: lines of constant φ (curving), constant t_wb and constant h (nearly straight, roughly parallel), and constant v (slightly sloped). The saturation curve (φ = 1) bounds the chart.
- Moving on the chart represents processes: horizontal is sensible heat transfer (w constant), slanted towards lower w is cooling with dehumidification, diagonal up-left at near-constant h is evaporative cooling (adiabatic humidification).
Standard air-conditioning processes (ideal models and why real ones differ)
- Sensible heating/cooling: w constant, only t_db changes. Real devices have small humidity change due to leakage or surface wetness.
- Humidification (by steam injection or water spray): increases w; with steam, t_db and h increase along a line of added enthalpy; with adiabatic water spray, h approximately constant while t_db decreases toward t_wb.
- Evaporative cooling (adiabatic humidification): ideally h ≈ constant, t_db drops toward the inlet wet-bulb while w increases; real pad efficiency η_evap < 1, limited by contact and losses.
- Cooling and dehumidification over a coil: air cools below its dew point; both t_db and w drop along a straight line toward the coil’s Apparatus Dew Point (ADP) on the saturation curve. Because not all air contacts the coldest surface, the leaving state is above the ADP; the Bypass Factor (BF) quantifies this.
- Mixing of air streams (e.g., outdoor + return): mass and energy balances on dry air and water vapour; the mixed state lies on the straight line joining the two states on the psychrometric chart, dividing the line in the ratio of dry-air mass flow rates.
Coil performance measures
- Apparatus Dew Point (ADP): the saturation state on the chart to which the coil would bring the air if contact were perfect (no bypass). Found by extending the process line to saturation.
- Bypass Factor (BF): fraction of air effectively bypassing the coil; BF = (leaving − ADP)/(entering − ADP). Applies component-wise (t_db, h, or w) for an ideal straight-line process. The contact factor (CF) or coil effectiveness = 1 − BF.
Comfort and loads (links to Refrigeration and Air Conditioning topic)
- Sensible heat vs latent heat loads: sensible affects t_db; latent affects w (moisture addition/removal). The Sensible Heat Factor (SHF) = Sensible/(Sensible + Latent) characterizes a process line’s slope on the chart.
- Typical indoor comfort design ranges (building codes/project specs decide exact values): about 22–26 °C DBT and 40–60% RH, with adequate ventilation; always use project-specific criteria for exams requiring a number.
Why real devices differ from ideal models
- Finite heat/mass transfer coefficients, non-uniform air velocities, surface wetness variations, coil fouling, and leakage cause deviations from constant-h lines in evaporative coolers and determine coil BF > 0. Saturation properties vary with pressure; charts assume a fixed barometric pressure.
Formulas
P = p_a + p_v
- Total pressure equals sum of dry-air and water-vapour partial pressures; P, p_a, p_v in kPa; applies under ideal-gas mixture assumption (Dalton’s law).
w = 0.622 p_v / (P − p_v)
- Humidity ratio w (kg_v/kg_da). p_v is vapour partial pressure (kPa), P total pressure (kPa). Valid for ideal-gas vapour/dry-air mixture.
φ = p_v / p_ws(t_db)
- Relative humidity (0–1). p_ws is saturation vapour pressure at dry-bulb temperature (kPa). Use with consistent pressure units.
h ≈ 1.005 t_db + w (2500 + 1.88 t_db)
- Enthalpy of moist air per kg of dry air, h in kJ/kg_da, t_db in °C, w in kg/kg_da. Reference: 0 °C liquid water and 0 °C dry air; commonly used in HVAC.
v ≈ (R_da T / P) (1 + 1.607 w)
- Specific volume per kg dry air, v in m³/kg_da. T in K, P in kPa, R_da ≈ 0.287 kJ/(kg·K) (same as kPa·m³/(kg·K)). Assumes ideal gases.
SH = w / (1 + w)
- Specific humidity (kg_v/kg_moist_air). Converts from humidity ratio.
Q̇_s ≈ ṁ_da · 1.005 (t_2 − t_1)
- Sensible heat transfer rate, kW if ṁ_da in kg_da/s and temperatures in °C. Assumes negligible change in cp with humidity.
Q̇_l ≈ ṁ_da · 2500 (w_2 − w_1)
- Latent heat transfer rate, kW if ṁ_da in kg_da/s and w in kg/kg_da. Approximate (uses 2500 kJ/kg); more exact latent enthalpy change is embedded in the full h equation.
Q̇_total = ṁ_da (h_2 − h_1)
- Total heat transfer rate across any duct element, kW, per kg_da/s basis, using moist-air enthalpy.
SHF = Q_s / (Q_s + Q_l)
- Sensible Heat Factor (dimensionless). Use consistent sensible and latent loads over the same control volume.
BF = (t_2 − t_ADP) / (t_1 − t_ADP) = (h_2 − h_ADP) / (h_1 − h_ADP) = (w_2 − w_ADP) / (w_1 − w_ADP)
- Coil bypass factor (dimensionless). t in °C, h in kJ/kg_da, w in kg/kg_da. Valid when the process line between entering state 1 and ADP is straight and leaving state 2 lies on that line.
η_evap = (t_in − t_out) / (t_in ��� t_wb,in)
- Direct evaporative cooler effectiveness (dimensionless). Assumes adiabatic device with no water heating and negligible fan heat.
Mixing: w_3 = (ṁ_1 w_1 + ṁ_2 w_2) / (ṁ_1 + ṁ_2), h_3 = (ṁ_1 h_1 + ṁ_2 h_2) / (ṁ_1 + ṁ_2)
- Mixed state of two streams (subscript 3), basis per kg dry air. Mass flow rates of dry air ṁ_i in kg_da/s.
Worked examples
Given: t_db = 30.0 °C; φ = 60%; P = 101.325 kPa.
Find: w, T_dp, h, v.
Data: Saturation pressure at 30 °C, p_ws(30 °C) ≈ 4.241 kPa.
Steps:
- Vapour partial pressure: p_v = φ · p_ws = 0.60 × 4.241 = 2.5446 kPa.
- Humidity ratio: use
w = 0.622 p_v / (P − p_v).- Numbers: w = 0.622 × 2.5446 / (101.325 − 2.5446) = 1.5827 / 98.7804 = 0.01602 kg/kg_da.
- Dew-point temperature T_dp: solve p_ws(T_dp) = p_v = 2.5446 kPa.
- Interpolating between tabulated p_ws: T_dp ≈ 21.4 °C.
- Enthalpy:
h = 1.005 t_db + w (2500 + 1.88 t_db).- Numbers: h = 1.005×30 + 0.01602×(2500 + 1.88×30) = 30.15 + 0.01602×2556.4 = 30.15 + 40.90 = 71.05 kJ/kg_da.
- Specific volume:
v = (R_da T / P) (1 + 1.607 w)with T = 303.15 K.- Numbers: v = (0.287×303.15 / 101.325) × (1 + 1.607×0.01602) = (87.0 / 101.325) × 1.0257 = 0.8586 × 1.0257 = 0.881 m³/kg_da.
Answer: w = 0.01602 kg/kg_da, T_dp ≈ 21.4 °C, h ≈ 71.05 kJ/kg_da, v ≈ 0.881 m³/kg_da.
Example 2 — Mixing + cooling coil with BF (GATE style)
- Given:
- Outdoor air (OA): t_db1 = 40.0 °C, φ1 = 30%, P = 101.325 kPa.
- Return air (RA): t_db2 = 25.0 °C, φ2 = 50%.
- Mixing: 30% OA and 70% RA by dry-air mass to form mixed air (MA).
- Cooling coil: BF = 0.15. Leaving supply air (SA) temperature t_2 = 15.0 °C.
- Find: (a) Coil ADP, (b) SA humidity ratio and enthalpy, (c) moisture removed and cooling load per kg of supply air.
- Data: p_ws(40 °C) ≈ 7.375 kPa; p_ws(25 °C) ≈ 3.169 kPa; p_ws(15 °C) ≈ 1.705 kPa. R_da ≈ 0.287 kJ/(kg·K).
- Steps:
- OA state: p_v1 = 0.30×7.375 = 2.2125 kPa.
w1 = 0.622 p_v1 / (P − p_v1) = 0.622×2.2125 / (101.325 − 2.2125) = 1.376 / 99.1125 = 0.01388 kg/kg_da.h1 = 1.005×40 + 0.01388×(2500 + 1.88×40) = 40.20 + 0.01388×2575.2 = 40.20 + 35.74 = 75.94 kJ/kg_da.
- RA state: p_v2 = 0.50×3.169 = 1.5845 kPa.
w2 = 0.622×1.5845 / (101.325 − 1.5845) = 0.9855 / 99.7405 = 0.00988 kg/kg_da.h2 = 1.005×25 + 0.00988×(2500 + 1.88×25) = 25.125 + 0.00988×2547.0 = 25.125 + 25.15 = 50.28 kJ/kg_da.
- Mixed air (30% OA, 70% RA):
w_MA = 0.3 w1 + 0.7 w2 = 0.3×0.01388 + 0.7×0.00988 = 0.01108 kg/kg_da.h_MA = 0.3 h1 + 0.7 h2 = 0.3×75.94 + 0.7×50.28 = 57.98 kJ/kg_da.- Find t_MA from
h = 1.005 t + w (2500 + 1.88 t): t_MA = [h − 2500 w]/[1.005 + 1.88 w] = (57.98 − 27.70)/(1.005 + 0.0208) = 30.28/1.0258 = 29.53 °C.
- Coil ADP using BF on temperature:
BF = (t_2 − t_ADP)/(t_MA − t_ADP)→t_ADP = (t_2 − BF·t_MA)/(1 − BF).- Numbers: t_ADP = (15.0 − 0.15×29.53)/0.85 = (15.0 − 4.4295)/0.85 = 10.5705/0.85 = 12.44 °C.
- Saturated properties at ADP (approx.): p_ws(12.44 °C) ≈ 1.45 kPa.
w_ADP = 0.622×1.45 / (101.325 − 1.45) = 0.9029 / 99.875 = 0.00904 kg/kg_da.h_ADP = 1.005×12.44 + 0.00904×(2500 + 1.88×12.44) = 12.50 + 0.00904×2523.37 = 12.50 + 22.80 = 35.30 kJ/kg_da.
- Leaving SA state using BF on w and h:
w_SA = w_ADP + BF (w_MA − w_ADP) = 0.00904 + 0.15×(0.01108 − 0.00904) = 0.00935 kg/kg_da.h_SA = h_ADP + BF (h_MA − h_ADP) = 35.30 + 0.15×(57.98 − 35.30) = 35.30 + 3.40 = 38.70 kJ/kg_da.- Check with t_2 = 15 °C:
h = 1.005×15 + 0.00935×(2500 + 1.88×15) = 15.08 + 0.00935×2528.2 = 15.08 + 23.62 = 38.70 kJ/kg_da(consistent).
- Moisture removed per kg of supply air (mass basis per kg_da):
Δw = w_MA − w_SA = 0.01108 − 0.00935 = 0.00173 kg/kg_da. - Cooling load per kg of supply air:
q_total = h_MA − h_SA = 57.98 − 38.70 = 19.28 kJ/kg_da.- Sensible part (approx.):
q_s ≈ 1.005 (t_MA − t_2) = 1.005×(29.53 − 15.0) = 14.60 kJ/kg_da. - Latent (approx.):
q_l ≈ 2500 Δw = 2500×0.00173 = 4.33 kJ/kg_da. - SHF ≈ 14.60/(14.60 + 4.33) = 0.77 (small difference vs exact enthalpy split due to approximations).
- Sensible part (approx.):
- OA state: p_v1 = 0.30×7.375 = 2.2125 kPa.
- Answers: (a) ADP ≈ 12.44 °C; (b) SA w ≈ 0.00935 kg/kg_da, h ≈ 38.70 kJ/kg_da; (c) Moisture removed ≈ 0.00173 kg/kg_da, cooling load ≈ 19.28 kJ/kg_da.
- Given:
Common mistakes
- Using relative humidity directly in energy balances; always convert to p_v then to w, and then to h.
- Forgetting that psychrometric charts are at a fixed pressure; using sea-level charts at high altitude introduces noticeable errors in w, h, and v.
- Applying BF formula only with temperature; for accuracy the BF relation should hold along the straight process line, so using h or w is often better when moisture change is significant.
- Assuming evaporative cooling is exactly constant enthalpy when pump/fan heat or water temperature rise matter; small deviations can affect sizing.
- Using 2500 kJ/kg for latent heat blindly; acceptable for quick estimates, but the h formula already embeds temperature dependence for better accuracy.
For GATE ME
- Definitions and distinctions: w vs specific humidity, RH vs degree of saturation, DBT/WBT/DP relations.
- Chart reading: identify states and processes, locate ADP and BF, interpret SHF lines.
- Numericals:
- Property calculations from DBT–RH or DBT–WBT pairs (often via chart/table; some papers give p_ws data).
- Mixing of two air streams; compute mixed state and process line segment ratios.
- Cooling and dehumidification through a coil: given BF/ADP/SHF and one leaving/entering state, find the others; compute loads, moisture removal.
- Evaporative cooler effectiveness and outlet state from inlet DBT/WBT and device η.
- Practice suggestions:
- Be fast at converting RH to w using p_ws(T) and Dalton’s law; memorize the workflow and keep a small set of common p_ws values (15, 25, 30, 35, 40 °C) at hand for mock tests.
- Draw clean psychrometric sketches; process lines and intersections (e.g., SHF line with saturation for ADP) are easier to reason with visually even if you compute numerically.
- Verify dimensional consistency (kJ/kg_da, m³/kg_da) and keep “per kg dry air” as your basis throughout.
Quick check
- At P = 101.325 kPa, t_db = 35 °C, φ = 40%. What is the first step to find w?
- Define the bypass factor (BF) for a cooling coil in terms of temperatures.
- For ideal evaporative cooling, which property of moist air remains approximately constant?
Answers: 1) Compute p_v = φ p_ws(35 °C) and then w = 0.622 p_v/(P − p_v). 2) BF = (t_leaving − t_ADP)/(t_entering − t_ADP). 3) Enthalpy h (approximately constant along the adiabatic humidification line).