Three-phase systems: star and delta

Three-phase systems: definitions, star (Y) and delta (Δ) connections, line–phase relationships, phasors, power in balanced systems, and typical exam numericals.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Three-phase systems are the backbone of electric power generation, transmission and use in industry. Engineers choose star (Y) or delta (Δ) connections to meet voltage, current and power needs of motors, heaters and distribution networks efficiently.

Key ideas

  • A balanced three-phase system has equal phase voltages and equal phase impedances (for loads), with phase currents equal in magnitude and displaced by 120°.

  • Phase sequence (or order) is the order in which the phase voltages reach their maximum positive value (e.g., R–Y–B). Reversing any two lines reverses the sequence.

  • Lines, phases, and connections

    • Phase (or line-to-neutral) voltage Vph: the voltage of one phase winding or load branch, measured across that phase element.
    • Line (or line-to-line) voltage VL: the voltage between any two lines (conductors) of the three-phase system.
    • Phase current Iph: the current through a single phase element (winding or load branch).
    • Line current IL: the current in a line conductor feeding the network.
    • In a three-phase, three-wire system, there are three line conductors; in a four-wire system, an additional neutral conductor carries the return current (useful for unbalanced star loads).
  • Star (Y) connection

    • In a star (Y) connection, one end of each of the three phase elements is joined to a common neutral point; the other ends are connected to the three lines.
    • Relationships for a balanced star system:
      • Line-to-line voltage is the phasor difference of two phase voltages. Magnitudes: VL = √3·Vph.
      • Line current equals phase current: IL = Iph.
      • Line voltage leads the corresponding phase voltage by 30° (for R–Y–B sequence with V_RN as reference).
    • Neutral current in a perfectly balanced star load is zero (the three phase currents sum vectorially to zero). With a neutral wire present, it carries the current due to any unbalance.
  • Delta (Δ) connection

    • In a delta (Δ) connection, the three phase elements are connected end-to-end to form a closed loop. Each line is connected to a junction of two elements.
    • Relationships for a balanced delta system:
      • Line-to-line voltage equals phase voltage: VL = Vph.
      • Line current is √3 times phase current: IL = √3·Iph.
      • Line current lags the corresponding phase current by 30° (for R–Y–B sequence with V_RN as reference).
  • Phasor basis and derivations (balanced systems)

    • Assume phase sequence R–Y–B and choose the R-phase voltage as reference: V_RN = V∠0°, V_YN = V∠−120°, V_BN = V∠+120°.
    • Star: V_RY = V_RN − V_YN = V[∠0° − (∠−120°)] = √3·V∠+30° in magnitude-angle form. Hence |V_RY| = √3·|V_RN|; similarly for other line voltages. Currents: I_R = V_RN/Z_ph, etc., with IL = Iph in magnitude.
    • Delta: V_RY appears directly across one phase element, so Vph = VL. Line current at R is the vector difference of the two adjacent phase currents, giving |IL| = √3·|Iph|.
  • Power in three-phase systems (balanced, sinusoidal steady-state)

    • Instantaneous power in each phase varies with time, but in a balanced three-phase load the sum is constant (no pulsation) at frequency 0 Hz.
    • Per-phase power: Pph = Vph·Iph·cosφ, where φ is the load power-factor angle (current lag positive for inductive).
    • Total active power: P = 3·Vph·Iph·cosφ = √3·VL·IL·cosφ (balanced only).
    • Total reactive power: Q = 3·Vph·Iph·sinφ = √3·VL·IL·sinφ (balanced only). By sign convention, Q > 0 for inductive (lagging) loads and Q < 0 for capacitive (leading) loads.
    • Total apparent power: S = 3·Vph·Iph = √3·VL·IL. Power factor PF = cosφ = P/S.
  • Source vs load connections

    • A three-phase generator (alternator) windings are commonly connected in star to allow a neutral; many distribution systems are star at the source. Loads can be star or delta depending on voltage and current requirements.
    • For the same line voltage, a delta-connected load sees higher phase voltage (equal to VL), so for the same impedance magnitude it draws higher current and more power than star.
  • Neutral and unbalance (brief)

    • In an unbalanced star load with neutral connected, each phase voltage remains equal to the source phase voltage; neutral carries the unbalance current.
    • In an unbalanced star load without neutral, the neutral point “floats” and phase voltages become unequal; analysis requires per-phase network solution (outside the balanced derivations shown here).
  • Power measurement (two-wattmeter method; brief exam-relevant note)

    • In a three-wire, balanced or unbalanced, three-phase system, two wattmeters connected to measure power in two lines (third line common return) give readings W1 and W2. Total active power P = W1 + W2 for any load. For a balanced load, PF angle φ can be found from tanφ = √3·(W1 − W2)/(W1 + W2). One wattmeter may read negative when φ > 60° (low PF lagging).
  • What to draw (exam diagrams)

    • Neatly draw:
      1. Star connection: three impedances with one end joined at neutral N; free ends labeled R, Y, B; line voltages VL between lines; phase voltages V_RN, V_YN, V_BN from lines to N; line currents in R, Y, B.
      2. Delta connection: three impedances in a triangle; each corner connected to lines R, Y, B; show phase currents around the delta and line currents entering each corner.
      3. Phasor diagram for balanced star: V_RN at 0°, V_YN at −120°, V_BN at +120°, and line voltage V_RY leading V_RN by 30°, with magnitudes showing √3 relation.

Formulas

V_L = √3·V_ph — Line-to-line and phase voltage relation in balanced star; V_L (V), V_ph (V).

I_L = I_ph — Line and phase current relation in balanced star; I_L (A), I_ph (A).

V_L = V_ph — Line-to-line and phase voltage relation in balanced delta; V_L (V), V_ph (V).

I_L = √3·I_ph — Line and phase current relation in balanced delta; I_L (A), I_ph (A).

P = 3·V_ph·I_ph·cosφ = √3·V_L·I_L·cosφ — Total active power of a balanced three-phase load; P (W), φ is power-factor angle.

Q = 3·V_ph·I_ph·sinφ = √3·V_L·I_L·sinφ — Total reactive power of a balanced three-phase load; Q (var).

S = 3·V_ph·I_ph = √3·V_L·I_L — Total apparent power of a balanced three-phase load; S (VA).

PF = cosφ = P/S — Power factor definition; unitless, 0 to 1 (lagging/leading indicates sign of φ).

tanφ = √3·(W1 − W2)/(W1 + W2) — Two-wattmeter method PF (balanced load); W1, W2 in watts; φ is load PF angle. Q = √3·(W1 − W2) — Reactive power by two-wattmeter method (balanced load); Q (var).

I_ph = V_ph/|Z_ph| — Phase current magnitude for a per-phase impedance Z_ph; V_ph (V), Z_ph (Ω).

Z_ph = R ± jX — Per-phase impedance; R (Ω), X (Ω); +jX for inductive (lagging), −jX for capacitive (leading).

Worked examples

Given: Line voltage VL = 400 V (three-wire), balanced star load with per-phase impedance Z_ph = 8 + j6 Ω (inductive), frequency not needed for steady-state magnitudes. Find: Line current IL, per-phase current Iph (magnitude and angle), total P, Q, and S, and PF. Steps:

  1. Phase voltage: V_ph = VL/√3 = 400/1.732 = 230.94 V.
  2. |Z_ph| = √(8² + 6²) = √(64 + 36) = 10 Ω; angle of Z_ph = arctan(6/8) = 36.87° (inductive).
  3. Phase current magnitude: I_ph = V_ph/|Z_ph| = 230.94/10 = 23.094 A. Current lags voltage by 36.87°: I_ph = 23.094∠−36.87° A.
  4. Star connection ⇒ I_L = I_ph = 23.094 A; PF = cosφ = cos36.87° = 0.8 (lagging).
  5. Apparent power: S = √3·V_L·I_L = 1.732·400·23.094 = 16,000 VA.
  6. Active power: P = S·PF = 16,000·0.8 = 12,800 W = 12.8 kW.
  7. Reactive power: Q = √(S² − P²) = √(16,000² − 12,800²) = 9,600 var (or Q = S·sinφ = 16,000·0.6 = 9,600 var). Final: IL = Iph = 23.094 A at −36.87°; S = 16.0 kVA; P = 12.8 kW; Q = 9.60 kvar; PF = 0.8 lagging. Answer: IL = 23.094 A; P = 12.8 kW; Q = 9.60 kvar; S = 16.0 kVA; PF = 0.8 lag.
  • Example 2: Balanced delta-connected resistive load Given: Line voltage VL = 415 V, delta-connected load with per-phase resistance R_ph = 20 Ω (purely resistive, φ = 0). Find: Phase current I_ph, line current I_L, and total power P. Steps:

    1. Delta ⇒ V_ph = V_L = 415 V.
    2. Phase current: I_ph = V_ph/R_ph = 415/20 = 20.75 A.
    3. Line current: I_L = √3·I_ph = 1.732·20.75 = 35.95 A.
    4. Total power: P = √3·V_L·I_L·cosφ = 1.732·415·35.95·1 = 25,834 W ≈ 25.83 kW (check: 3·V_ph·I_ph = 3·415·20.75 = 25,833.75 W, same within rounding). Final: I_ph = 20.75 A; I_L = 35.95 A; P ≈ 25.83 kW. Answer: I_L = 35.95 A; P = 25.83 kW.
  • Example 3: Find per-phase impedance of a balanced star load from total power and PF Given: Line voltage VL = 440 V, total active power P = 30 kW, PF = 0.9 lagging, balanced star connection. Find: Per-phase impedance Z_ph = R + jX. Steps:

    1. Line current from P = √3·V_L·I_L·cosφ: I_L = P/(√3·V_L·cosφ) = 30,000/(1.732·440·0.9). Compute denominator: 1.732·440 = 762.08; times 0.9 = 685.872. Hence I_L = 30,000/685.872 = 43.73 A.
    2. Star ⇒ I_ph = I_L = 43.73 A.
    3. Phase voltage: V_ph = V_L/√3 = 440/1.732 = 254.03 V.
    4. Magnitude of per-phase impedance: |Z_ph| = V_ph/I_ph = 254.03/43.73 = 5.81 Ω.
    5. PF angle: φ = arccos(0.9) = 25.84° (lagging). Then R = |Z|·cosφ = 5.81·0.9 = 5.23 Ω; X = |Z|·sinφ = 5.81·0.436 = 2.53 Ω. Final: Z_ph ≈ 5.23 + j2.53 Ω (lagging). Answer: Z_ph = 5.23 + j2.53 Ω.

Common mistakes

  • Dropping the √3 factor in three-phase power: Using P = V_L·I_L·cosφ instead of P = √3·V_L·I_L·cosφ for balanced loads.
  • Using wrong φ sign or PF type: Not stating lagging/leading; using sinφ or cosφ inconsistently in P and Q.
  • Confusing phase sequence effects: Forgetting that reversing any two lines reverses sequence and can change motor rotation direction.
  • Forgetting that neutral current is zero only for a perfectly balanced star load; assuming zero in unbalanced cases without checking.
  • In delta, summing line currents arithmetically instead of vectorially (they are 120° apart), or using 3× instead of √3×.
  • Power measurement: Interpreting a negative wattmeter reading as an error rather than reversing its connections (or taking magnitude and noting sign) when PF is low.

For your exam

  • Derivations (common):
    • Star: Derive V_L = √3·V_ph using phasor subtraction V_RY = V_RN − V_YN with 120° displacement; show 30° phase shift.
    • Delta: Derive I_L = √3·I_ph by vector difference of adjacent phase currents.
    • Three-phase power: Show P = 3·V_ph·I_ph·cosφ and simplify to √3·V_L·I_L·cosφ for balanced loads.
    • Two-wattmeter method PF relation tanφ = √3·(W1 − W2)/(W1 + W2) (state assumptions: three-wire, sinusoidal steady state).
  • Numericals: Given VL and load per-phase impedance, compute IL, P, Q, S, PF for star or delta; given P, VL, PF, find IL and Z_ph; convert a practical load requirement between star and delta ratings (explain qualitatively if transformation is from another topic).
  • Diagrams: Clean star and delta circuit diagrams with labels; balanced phasor diagrams (phase and line voltages); show angles (120° separation, 30° relations).
  • Full-marks answers include: clear assumptions (balanced, sinusoidal, sequence), correct formula with justification, correct units throughout, neat phasor/circuit diagrams with labels, and final boxed values.

Quick check

  1. In a balanced star connection, if V_L = 415 V, what is V_ph?
  2. In a balanced delta load with I_ph = 12 A, what is I_L?
  3. A balanced three-phase load draws I_L = 10 A at V_L = 400 V with PF = 0.8 lagging. What is the active power P?

Answers: 1) V_ph = 415/√3 = 239.6 V. 2) I_L = √3·12 = 20.78 A. 3) P = √3·400·10·0.8 = 5.55 kW (approximately).