Single-phase transformer

Single-phase transformer: principle, EMF equation, turns ratio, equivalent circuit, losses, efficiency and max-efficiency condition, voltage regulation, OC/SC tests, phasor diagram, worked numericals.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Single-phase transformers change AC voltage levels with high efficiency, enabling safe distribution (e.g., 11 kV to 230 V) and isolation. Engineers meet them in power systems, electronic power supplies, instrumentation, and when testing equipment that needs specific voltages.

Key ideas

  • Primary winding: The coil connected to the input AC source.
  • Secondary winding: The coil connected to the load.
  • Core: A ferromagnetic path (usually laminated silicon steel) that guides magnetic flux and reduces reluctance. Laminations reduce eddy currents.
  • Mutual induction (principle of operation): An alternating current in the primary produces a time-varying magnetic flux in the core, which links both windings and induces EMFs in them according to Faraday’s law. Thus, power transfers magnetically without electrical contact.

Exact statements and standard derivations commonly asked in exams:

  1. Ideal transformer assumptions and relations
  • Ideal transformer (definition): A transformer with zero winding resistance, zero leakage flux, infinite core permeability (so zero magnetizing current), and zero core loss. Frequency is constant.
  • Turns ratio: a = N1/N2, where N1 and N2 are the primary and secondary turns.
  • For the ideal transformer under sinusoidal steady state: V1/V2 = N1/N2 = a, and I1/I2 = N2/N1 = 1/a. Input power equals output power (100% efficiency), so V1·I1 = V2·I2.
  1. EMF equation (sinusoidal flux)
  • Consider sinusoidal core flux φ(t) = Φm sin(ωt), where Φm is peak flux in weber. By Faraday’s law, instantaneous EMF e = −N (dφ/dt) = −N Φm ω cos(ωt). The RMS value over a cycle is E = 4.44 f N Φm. Derivation steps:
    • Average value of |e| over a half-cycle is 4 f N Φm (since Δφ = 2Φm over T/2 = 1/(2f)).
    • The form factor of a sine wave EMF is 1.11; hence RMS E = 1.11 × average = 1.11 × 4 f N Φm = 4.44 f N Φm.
    • For primary and secondary: E1 = 4.44 f N1 Φm, E2 = 4.44 f N2 Φm.
  1. No-load behavior and phasors
  • With secondary open, a small no-load current I0 flows in the primary, lagging V1 by nearly 90°, to establish flux. It has two components:
    • Core-loss (or working) component Iw in phase with V1, supplying core loss (hysteresis + eddy currents).
    • Magnetizing component Iμ in quadrature (lagging) with V1, establishing flux.
  • Phasor diagram to draw and label: Take V1 as reference horizontal to the right. Draw Iw in phase with V1 (colinear), Iμ downward (lagging by 90°), and I0 as the vector sum of Iw and Iμ. Induced EMF E1 is approximately equal and opposite to V1 (E1 ≈ −V1) in magnitude under no-load; indicate E1 180° out of phase with V1.
  1. Practical transformer equivalent circuit
  • Include winding resistances R1, R2 and leakage reactances X1, X2 in series with their windings.
  • Core losses represented by a parallel core-loss resistance R0 (across the magnetizing branch), and magnetization by magnetizing reactance X0 (inductive), both placed in shunt across the primary.
  • The exact equivalent circuit has R0 and X0 in parallel across the ideal transformer; series R and X are with each winding. For calculations, we often refer all secondary parameters to the primary using the square of the turns ratio: Z′2 = a2 Z2.
  • Diagram to draw and label: From left, V1 source to series R1 and X1, then ideal transformer to secondary series R2 and X2, with the shunt branch (R0 || jX0) connected across the ideal primary. Alternatively, show the approximate circuit with R0 and X0 omitted for load-calculation and using referred R′2, X′2 in series with R1, X1.
  1. Losses in a transformer
  • Copper loss: I2R loss in windings, varies with square of load current. At any load fraction x of full-load current, Pcu(x) = x2 Pcu,fl.
  • Core loss: Sum of hysteresis and eddy-current losses. At fixed frequency and rated voltage, it is approximately constant with load.
    • Hysteresis loss: Ph ≈ Kh f Bmax^n (n ≈ 1.6–2 for CRGO steel).
    • Eddy-current loss: Pe ≈ Ke f² Bmax² t² (t = lamination thickness). Lamination reduces Pe by lowering t.
  • Stray losses: Additional losses due to leakage flux in structural parts; often included within measured copper loss during SC test.
  1. Efficiency and condition for maximum efficiency
  • Efficiency (η): η = Pout/Pin = Pout/(Pout + Pcu + Pcore). For a given load fraction x and power factor cosφ, Pout = x·S·cosφ (S is rated kVA). Pcu = x2·Pcu,fl; Pcore ≈ constant.
  • Condition for maximum efficiency: Occurs at the load for which variable loss equals constant loss: x2 Pcu,fl = Pcore. At this x, η is maximum.
  • All-day (energy) efficiency: For distribution use, defined over 24 hours as (Energy output over 24 h) / (Energy input over 24 h). Since core loss is present 24 h and copper loss varies with load curve, all-day efficiency may be lower than ordinary efficiency.
  1. Voltage regulation
  • Voltage regulation (at a given power factor): The change in secondary terminal voltage when full load is applied, keeping primary voltage and frequency constant, expressed as a percentage of full-load voltage: %VR = [(Vnl − Vfl)/Vfl] × 100.
  • Approximate expression using series parameters referred to secondary (or primary) side: VR ≈ (I·Req cosφ ± I·Xeq sinφ)/V, where + for lagging PF, − for leading PF, and all quantities are on the same side and at rated current and voltage.
  1. Open-circuit (OC) and short-circuit (SC) tests (to find equivalent circuit and efficiency without full-load)
  • OC test: Usually on LV side (to minimize voltage requirement), with HV side open.
    • Apply rated voltage, measure input power W0, current I0, and voltage V0.
    • Since current is small, copper loss is negligible; W0 ≈ core loss.
    • Compute core-loss resistance R0 = V02/W0, core-loss component Iw = W0/V0, magnetizing component Iμ = √(I02 − Iw2), and magnetizing reactance X0 = V0/Iμ.
  • SC test: Usually on HV side, with LV side shorted through an ammeter.
    • Apply just enough voltage Vsc to circulate rated current Isc; measure input power Wsc and current.
    • Core loss is negligible (low V), so Wsc ≈ full-load copper loss on the tested side.
    • Equivalent series parameters referred to the test side: Req = Wsc/Isc2, Zeq = Vsc/Isc, Xeq = √(Zeq2 − Req2).
  • Using OC and SC test results, you can estimate efficiency at any load and voltage regulation at a given PF without loading the transformer.
  1. Polarity and dot convention (brief)
  • Polarity marks (dot convention) indicate instantaneous polarities of induced EMFs. When currents enter dotted ends simultaneously, the mutual EMF is positive. Practical polarity test uses low-voltage connections and a voltmeter to ensure correct series aiding/opposition.
  1. kVA rating and isolation
  • Transformers are rated in kVA because copper loss depends on current and core loss on voltage; neither depends on power factor directly. A transformer also provides galvanic isolation (two-winding type), improving safety and noise immunity.

Formulas

E = 4.44·f·N·Φm

  • E: RMS induced EMF per winding (volt, V); f: frequency (hertz, Hz); N: turns (dimensionless); Φm: maximum magnetic flux in core (weber, Wb). Applies for sinusoidal flux.

V1 / V2 = N1 / N2 = a

  • V1, V2: RMS voltages of primary, secondary (V); N1, N2: turns; a: turns ratio. Ideal transformer or approximate when voltage drops are small.

I1 / I2 = N2 / N1 = 1 / a

  • I1, I2: RMS currents in primary, secondary (ampere, A). Ideal transformer.

Z′2 = a²·Z2

  • Z′2: secondary impedance referred to primary (ohm, Ω); Z2: actual secondary impedance; a: turns ratio. Similarly, Z′1 = Z1/a² when referred to secondary.

Pcu(x) = x²·Pcu,fl

  • Pcu(x): copper loss at load fraction x; Pcu,fl: full-load copper loss (watt, W). Assumes temperature steady-state at comparable operating point.

η = Pout / Pin = Pout / (Pout + Pcu + Pcore)

  • η: efficiency (dimensionless or %); Pout: output power (W); Pin: input power (W); Pcu: copper loss (W); Pcore: core loss (W). Sinusoidal steady state.

x(at max η) = √(Pcore / Pcu,fl)

  • Load fraction x for maximum efficiency. Pcore: core loss at rated V and f (W); Pcu,fl: full-load copper loss (W).

%VR = [(Vnl − Vfl) / Vfl] × 100

  • %VR: percent voltage regulation (%); Vnl: no-load secondary voltage (V); Vfl: full-load secondary voltage at specified PF (V). Rated primary voltage and frequency maintained.

VR ≈ (I·Req·cosφ ± I·Xeq·sinφ) / V

  • VR: per-unit or fraction voltage regulation; I: rated current on same side as Req, Xeq (A); Req, Xeq: equivalent resistance and reactance on that side (Ω); V: rated voltage on that side (V); cosφ: load power factor; use + for lagging, − for leading.

S (kVA) = V·I / 1000

  • S: apparent power (kilovolt-ampere, kVA); V: RMS rated voltage (V); I: RMS rated current (A).

Ph ≈ Kh·f·Bmaxⁿ ; Pe ≈ Ke·f²·Bmax²·t²

  • Ph: hysteresis loss (W); Pe: eddy-current loss (W); Kh, Ke: material/geometric constants; Bmax: peak flux density (tesla, T); f: frequency (Hz); t: lamination thickness (m). Material-dependent approximation.

Worked examples

Example 1: EMF equation application and turns decision Given: A single-phase core has maximum flux Φm = 0.012 Wb at f = 50 Hz. The primary has N1 = 1200 turns. Find E1 (RMS). Also, for a 230 V secondary at the same flux and frequency, find N2 (nearest integer).

Steps:

  1. Formula: E1 = 4.44·f·N1·Φm
  2. Numbers: E1 = 4.44 × 50 × 1200 × 0.012 V
  3. Compute: 4.44×50 = 222; 222×1200 = 266400; 266400×0.012 = 3196.8 V Answer: E1 ≈ 3.197 kV (RMS).

For secondary turns:

  1. Formula: N2 = E2 / (4.44·f·Φm)
  2. Numbers: N2 = 230 / (4.44 × 50 × 0.012)
  3. Compute denominator: 4.44×50 = 222; 222×0.012 = 2.664; N2 = 230 / 2.664 = 86.33 Answer: N2 ≈ 86 turns.

Example 2: OC/SC tests to find equivalent circuit and efficiency A 5 kVA, 230/115 V, 50 Hz single-phase transformer gives the following tests:

  • OC test on LV (115 V) side: V0 = 115 V, I0 = 0.60 A, W0 = 40 W.
  • SC test on HV (230 V) side with LV shorted: Vsc = 18 V to circulate Isc = 21.739 A (rated HV current), Wsc = 160 W. Find: R0, X0 referred to LV; Req, Xeq referred to HV; full-load efficiency at 0.8 power factor lagging; and load for maximum efficiency.

OC test (LV side parameters):

  1. R0 = V0² / W0 = 115² / 40 Ω = 13225 / 40 = 330.625 Ω.
  2. Iw = W0 / V0 = 40 / 115 A = 0.3478 A.
  3. Iμ = √(I0² − Iw²) = √(0.60² − 0.3478²) A = √(0.36 − 0.121) = √0.239 = 0.4889 A.
  4. X0 = V0 / Iμ = 115 / 0.4889 Ω = 235.3 Ω.

SC test (HV side equivalent series parameters at rated current):

  1. Req = Wsc / Isc² = 160 / (21.739)² Ω. Compute (21.739)² ≈ 472.0; Req ≈ 160 / 472.0 = 0.339 Ω.
  2. Zeq = Vsc / Isc = 18 / 21.739 Ω = 0.828 Ω.
  3. Xeq = √(Zeq² − Req²) = √(0.828² − 0.339²) Ω = √(0.685 − 0.115) = √0.570 = 0.755 Ω.

Full-load efficiency at 0.8 lagging:

  • Rated S = 5 kVA, so Pout,fl = S·cosφ = 5×0.8 = 4 kW.
  • Core loss ≈ W0 = 40 W (at rated V, f).
  • Full-load copper loss ≈ Wsc = 160 W (at rated current).
  • Pin = Pout + losses = 4000 + (40 + 160) = 4200 W.
  • ηfl = 4000 / 4200 = 0.95238 = 95.24%. Answer: Full-load efficiency ≈ 95.24% at 0.8 lag.

Load for maximum efficiency:

  • Condition: x²·Pcu,fl = Pcore ⇒ x = √(Pcore/Pcu,fl) = √(40/160) = √0.25 = 0.5 (i.e., 50% of full-load current).
  • Optional check of efficiency at x = 0.5, cosφ = 0.8: Pout = 0.5×5 kVA×0.8 = 2.0 kW; losses = 40 + (0.5)²×160 = 40 + 40 = 80 W; η = 2000 / 2080 = 96.15%. Answer: Maximum efficiency occurs at 50% load; at 0.8 lag it would be ≈ 96.15%.

Example 3: Approximate voltage regulation at lagging and leading PF Using the SC-test series parameters from Example 2 (referred to HV side): Req = 0.339 Ω, Xeq = 0.755 Ω. Rated HV current I = 21.739 A, rated HV voltage V = 230 V. Find %VR at 0.8 lagging and 0.8 leading power factor.

Formula: VR ≈ (I·Req·cosφ ± I·Xeq·sinφ) / V; use + for lagging, − for leading. With cosφ = 0.8, sinφ = 0.6.

Lagging 0.8 PF:

  1. Resistive drop term: I·Req·cosφ = 21.739×0.339×0.8 V = (7.3695)×0.8 = 5.8956 V.
  2. Reactive drop term: I·Xeq·sinφ = 21.739×0.755×0.6 V = (16.4129)×0.6 = 9.8477 V.
  3. Total drop = 5.8956 + 9.8477 = 15.7433 V; VR = 15.7433 / 230 = 0.06845 = 6.845%. Answer: %VR ≈ 6.85% at 0.8 lagging.

Leading 0.8 PF:

  1. Total drop = 5.8956 − 9.8477 = −3.9521 V.
  2. VR = −3.9521 / 230 = −0.01718 = −1.718%. Answer: %VR ≈ −1.72% at 0.8 leading (rise in voltage).

Common mistakes

  • Using Vfl in place of Vnl in the numerator or the wrong denominator in the voltage regulation definition; always use (Vnl − Vfl) divided by Vfl.
  • Ignoring that core loss is approximately constant with load at rated voltage/frequency; wrongly scaling core loss with load current.
  • In OC/SC tests, taking Wsc as Zeq directly or forgetting to compute Req = Wsc/Isc² first; also using wrong side (primary vs secondary) parameters in the regulation formula.
  • Not converting kVA to kW by multiplying by power factor when computing output power and efficiency.
  • Sign error in regulation for leading power factor; remember the reactive term subtracts for leading loads.
  • Forgetting to square the turns ratio when referring impedances (Z′ = a²Z), leading to large numerical errors.

For your exam

  • Derivations: EMF equation E = 4.44 f N Φm (step-by-step from sinusoidal flux), voltage/current/turns relations of ideal transformer, condition for maximum efficiency x = √(Pcore/Pcu,fl), approximate voltage regulation expression from equivalent circuit, OC/SC test parameter extraction (R0, X0, Req, Xeq).
  • Diagrams to draw: no-load phasor diagram (V1 reference, Iw in phase, Iμ lagging 90°, I0 vector sum, E1 opposite to V1), equivalent circuit (exact and approximate), practical core with primary/secondary on limbs and polarity dots. Label all voltages, currents, resistances/reactances. Also be prepared to draw loaded phasor diagrams (lagging and leading PF), showing V2, E2, and the drops I·Req and I·Xeq.
  • Numericals: EMF and turns calculation; OC/SC test data to find R0, X0, Req, Xeq; compute efficiency at specified load and PF; compute % voltage regulation for given PF; condition for maximum efficiency and value of max η.
  • Presentation tips: State assumptions (sinusoidal, constant frequency/voltage, neglecting shunt branch if using approximate circuit). Carry units throughout, show formulas before substituting numbers, and provide final answers in bold with proper SI units.

Quick check

  1. A 50 Hz transformer has Φm = 0.02 Wb and N = 800 turns. What is the RMS induced EMF of that winding?
  2. In an OC test at rated voltage, why is the wattmeter reading taken as core loss? In an SC test at rated current, why is the wattmeter reading taken as copper loss?
  3. A transformer has %VR = 5% at 0.8 lagging. Will the %VR at 0.8 leading be higher, lower, or possibly negative? Briefly state why.

Answers: 1) E = 4.44×50×800×0.02 = 3552 V (RMS). 2) In OC, current is small so copper loss is negligible; applied voltage is rated so core loss is representative. In SC, applied voltage is very low so core loss is negligible; rated current makes copper loss representative. 3) Lower and possibly negative, because the reactive drop term I·Xeq·sinφ subtracts for leading power factor.

Finished this topic? Mark it so your progress, study plan and readiness keep up.