Power and power factor in AC circuits

Power and power factor in AC circuits: active, reactive and apparent power; power triangle; instantaneous power; single- and three-phase power formulas; measurement (wattmeter, two-wattmeter method); effects of low power factor and its correction.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Key ideas

  • The average over one cycle is the active/real power P = (VmIm/2)cosφ = Vrms·Irms·cosφ.
  • Active (real) power P: Exact definition—Active power is the average rate of energy transfer over a cycle in an AC circuit. It is given by P = Vrms·Irms·cosφ. Unit: watt (W). Positive when the load consumes net energy.
  • Reactive power Q: Exact definition—Reactive power is the component of AC power that oscillates between source and reactive elements (L or C) and has zero average over a cycle. For sinusoidal steady state, Q = Vrms·Irms·sinφ. Unit: volt-ampere reactive (var). Positive Q indicates net inductive load (current lags), negative Q indicates net capacitive load (current leads). Average energy transfer due to Q over a cycle is zero.
  • Apparent power S: Exact definition—Apparent power is the product of RMS voltage and current, S = Vrms·Irms. Unit: volt-ampere (VA). It is the vector (complex) magnitude combining P and Q: S² = P² + Q².
  • Power factor (PF): Exact definition—Power factor is the ratio of active power to apparent power in an AC circuit: PF = P/S = cosφ for sinusoidal waveforms. If current lags voltage, the power factor is “lagging” (inductive); if current leads, it is “leading” (capacitive). True power factor for non-sinusoidal waveforms is PF = P/(Vrms·Irms) and equals (displacement power factor)×(distortion factor).
  • Power triangle: A right-angled triangle representing S as the hypotenuse, P on the adjacent axis, and Q on the opposite axis. Angle at P is φ. Exactly, S∠φ = P + jQ, with S² = P² + Q² and tanφ = Q/P.
    • Diagram to draw: A right triangle. Horizontal (x-axis) labeled P (kW) to the right. Vertical (y-axis) labeled Q (kVAr): up for inductive (+Q), down for capacitive (−Q). Hypotenuse from origin to the point (P,Q) labeled S (kVA). Angle φ between S and P axis.
  • Power in pure elements (sinusoidal steady state):
    • Pure resistor (R): φ = 0°, P = VI, Q = 0, p(t) ≥ 0 always.
    • Pure inductor (L): φ = +90°, P = 0, Q > 0, p(t) alternates equally positive/negative; average zero.
    • Pure capacitor (C): φ = −90°, P = 0, Q < 0, p(t) alternates equally; average zero.
  • Three-phase balanced circuits:
    • Line-to-line voltage VL, line current IL. For a balanced three-phase load,
      • Active power: P = √3·VL·IL·cosφ
      • Reactive power: Q = √3·VL·IL·sinφ
      • Apparent power: S = √3·VL·IL
    • These apply to both star and delta loads if VL and IL are line quantities and the load is balanced.
  • Measurement of power and power factor:
    • Single-phase: A single wattmeter measures P directly; with Vrms and Irms measured, PF = P/(V·I).
    • Two-wattmeter method (three-phase, 3-wire, balanced or unbalanced load): Two wattmeters measure W1 and W2 using line currents and line-to-line voltages.
      • Exact results for any (even unbalanced) load: Total three-phase active power P = W1 + W2.
      • For a balanced load specifically: tanφ = √3·(W1 − W2)/(W1 + W2) for lagging φ. Special cases: at unity PF, W1 = W2; at PF = 0.5 lag (φ = 60°), one wattmeter reads zero; for φ > 60° lag, one wattmeter reads negative (its current or voltage coil must be reversed to read upscale).
    • Diagram to draw for two-wattmeter method: Three-phase source with lines R, Y, B to the load. Wattmeter W1 has current coil in R line; its voltage (pressure) coil between R and Y lines. Wattmeter W2 has current coil in B line; its voltage coil between B and Y lines. Indicate polarities on coils and line directions.
  • Effect of power factor:
    • For given P and V, current I = P/(V·PF). Lower PF means higher current, causing higher I²R losses, larger voltage drops, and larger kVA ratings of generators/transformers/cables.
    • Utilities often levy penalties for low PF; improving PF reduces losses and frees capacity.
  • Power factor correction (PFC):
    • Objective: Reduce the phase angle φ (move operating point along the power triangle) so PF approaches unity.
    • Common method: Add shunt capacitors across the load (single-phase) or per phase (three-phase) to supply local reactive power (negative Q), thus reducing net Q drawn from the supply.
    • Exact sizing (single-phase): Required capacitor reactive power Qc = P·(tanφ1 − tanφ2), where φ1 is initial angle and φ2 is target angle (both lagging taken positive). Capacitance C = Qc/(ω·V²), with ω = 2πf and V the RMS voltage across the capacitor.
    • Three-phase capacitor banks:
      • Star (Y) connection, per-phase capacitance C: Total Qc = 3·Vph²·ω·C, where Vph = VL/√3.
      • Delta (Δ) connection, per-branch capacitance C: Total Qc = 3·VL²·ω·C.
    • Other methods (names only; see rotating machines topics): Synchronous condenser (over-excited synchronous motor), and phase advancers for induction motors.
  • Distortion vs displacement power factor (brief): If current is non-sinusoidal (harmonics), PF = P/(Vrms·Irms) < cosθ1 typically, where θ1 is the phase angle between fundamental voltage and current. Displacement PF = cosθ1; distortion factor = Irms(1)/Irms(total). In this topic, we mostly assume sinusoidal steady state unless stated.

Formulas

p(t) = v(t)·i(t) — Instantaneous power; p in W, v in V, i in A; always true. p(t) = (Vm·Im/2)[cosφ − cos(2ωt − φ)] — Instantaneous power for sinusoidal v and i; Vm, Im are peak values; ω in rad·s⁻¹; φ is current angle (lagging positive). P = (Vm·Im/2)·cosφ = Vrms·Irms·cosφ — Active (real) power; P in W; sinusoidal steady state. Q = Vrms·Irms·sinφ — Reactive power; Q in var; sinusoidal steady state; Q > 0 inductive, Q < 0 capacitive. S = Vrms·Irms — Apparent power; S in VA; sinusoidal or not. S² = P² + Q² — Power triangle relationship; sinusoidal steady state. PF = P/S = cosφ — Power factor for sinusoidal waveforms; dimensionless; φ is angle by which current lags/leads voltage. P3φ = √3·VL·IL·cosφ — Three-phase active power; VL line-to-line volts, IL line current, P in W; balanced. Q3φ = √3·VL·IL·sinφ — Three-phase reactive power; Q in var; balanced. S3φ = √3·VL·IL — Three-phase apparent power; S in VA; balanced. P = W1 + W2 — Two-wattmeter total active power in a three-phase 3-wire system; any load. tanφ = √3·(W1 − W2)/(W1 + W2) — Power factor angle from two-wattmeter readings; balanced load. I = P/(V·PF) — Current drawn by a single-phase load given P and PF; I in A, V in V, PF dimensionless. Qc = P·(tanφ1 − tanφ2) — Required capacitive kVAr to improve PF from cosφ1 to cosφ2 (lagging angles positive); Qc in var, P in W. C = Qc/(ω·V²) — Capacitance of shunt capacitor for single-phase PFC; C in F, Qc in var, V in V, ω = 2πf. Qc(Y) = 3·Vph²·ω·C — Total kVAr of a three-phase star capacitor bank; Vph in V, C per phase in F. Qc(Δ) = 3·VL²·ω·C — Total kVAr of a three-phase delta capacitor bank; VL in V, C per branch in F.

Worked examples

  1. Single-phase load: power, kVAr, current, and capacitor for PF correction Given: A 230 V, 50 Hz single-phase load takes 5.0 kW at power factor 0.70 lagging. Find (a) line current, (b) apparent power and reactive power, (c) the capacitor kVAr and capacitance needed to raise PF to 0.95 lagging, and (d) current after correction.

Step 1: Compute current before correction.

  • Formula: I = P/(V·PF)
  • Numbers: I = 5000 W / (230 V · 0.70) = 5000 / 161 = 31.06 A

Step 2: Compute apparent power S and reactive power Q.

  • S = P/PF = 5000/0.70 = 7142.86 VA = 7.143 kVA
  • cosφ1 = 0.70 ⇒ φ1 = arccos(0.70) ≈ 45.57°; tanφ1 = √(1 − 0.70²)/0.70 ≈ 1.0202
  • Q = P·tanφ1 = 5000 · 1.0202 = 5101 var = 5.101 kVAr (Check: S² − P² ≈ (7.143 kVA)² − (5 kW)² ≈ 51.02 − 25.00 = 26.02 kV² ⇒ Q ≈ 5.101 kVAr)

Step 3: Required capacitor kVAr to reach PF 0.95 (lagging).

  • cosφ2 = 0.95 ⇒ φ2 = arccos(0.95) ≈ 18.19°, tanφ2 ≈ 0.3287
  • Formula: Qc = P·(tanφ1 − tanφ2)
  • Numbers: Qc = 5000 · (1.0202 − 0.3287) = 5000 · 0.6915 = 3458 var = 3.458 kVAr

Step 4: Capacitance value (shunt across 230 V at 50 Hz).

  • Formula: C = Qc/(ω·V²), ω = 2πf = 314.159 rad·s⁻¹
  • Denominator: ω·V² = 314.159 · (230²) = 314.159 · 52,900 ≈ 16,619,011
  • C = 3458 / 16,619,011 = 2.08×10⁻⁴ F = 208 µF

Step 5: Current after correction to PF 0.95 lagging.

  • I₂ = P/(V·PF₂) = 5000 / (230 · 0.95) = 5000 / 218.5 = 22.88 A

Answer: (a) 31.06 A, (b) S = 7.143 kVA, Q = 5.101 kVAr, (c) Qc ≈ 3.458 kVAr, C ≈ 208 µF, (d) I₂ ≈ 22.88 A. Final answers: (a) 31.06 A; (b) 7.143 kVA and 5.101 kVAr; (c) 3.458 kVAr and 208 µF; (d) 22.88 A.

  1. Three-phase balanced system: power, kVAr, kVA, line current, and two-wattmeter readings Given: A balanced three-phase, 400 V (line-to-line), 50 Hz supply feeds a balanced load absorbing 30 kW at 0.8 power factor lagging. Find (a) kVA and kVAr, (b) line current, (c) readings of the two wattmeters W1 and W2 in the two-wattmeter method.

Step 1: Compute S and Q.

  • S = P/PF = 30 kW / 0.8 = 37.5 kVA
  • cosφ = 0.8 ⇒ φ = arccos(0.8) = 36.87°, tanφ = 0.75
  • Q = P·tanφ = 30 kW · 0.75 = 22.5 kVAr

Step 2: Line current for balanced load.

  • Formula: P = √3·VL·IL·cosφ ⇒ IL = P/(√3·VL·cosφ)
  • Numbers: IL = 30,000 / (1.73205 · 400 · 0.8) = 30,000 / 554.256 = 54.12 A

Step 3: Two-wattmeter readings for a balanced load.

  • Formulas: W1 = VL·IL·cos(30° − φ), W2 = VL·IL·cos(30° + φ)
  • Compute base: VL·IL = 400 · 54.12 = 21,648
  • Angles: 30° − 36.87° = −6.87° ⇒ cos = 0.9928; 30° + 36.87° = 66.87° ⇒ cos ≈ 0.3940
  • W1 = 21,648 · 0.9928 = 21,491 W ≈ 21.49 kW
  • W2 = 21,648 · 0.3940 = 8,524 W ≈ 8.52 kW
  • Check: W1 + W2 ≈ 30.01 kW ≈ P (rounding). Using tanφ = √3(W1 − W2)/(W1 + W2) gives tanφ ≈ 0.748 ≈ 0.75.

Answer: (a) S = 37.5 kVA, Q = 22.5 kVAr; (b) IL ≈ 54.12 A; (c) W1 ≈ 21.49 kW, W2 ≈ 8.52 kW. Final answers: (a) 37.5 kVA and 22.5 kVAr; (b) 54.12 A; (c) 21.49 kW and 8.52 kW.

  1. Instantaneous power expression and average power check Given: In a single-phase load, Vrms = 230 V, Irms = 10 A, current lags voltage by φ = 30°. Find (a) the instantaneous power p(t) expression, (b) its average value, and (c) whether p(t) becomes negative during a cycle.

Step 1: Express v and i in terms of RMS values.

  • Vm = √2·Vrms = 325.27 V; Im = √2·Irms = 14.142 A
  • v(t) = Vm sin(ωt), i(t) = Im sin(ωt − 30°)

Step 2: Instantaneous power.

  • Formula: p(t) = (Vm·Im/2)[cosφ − cos(2ωt − φ)]
  • Numbers: Vm·Im/2 = (325.27 · 14.142)/2 = (4600.0)/2 = 2300.0
  • p(t) = 2300[cos30° − cos(2ωt − 30°)] = 2300[0.8660 − cos(2ωt − 30°)] W

Step 3: Average power over a cycle.

  • P = Vrms·Irms·cosφ = 230 · 10 · 0.8660 = 1991.8 W
  • From p(t), the average of the cos(2ωt − 30°) term is zero; the average equals 2300 · 0.8660 = 1991.8 W, confirming the result.

Step 4: Sign of instantaneous power.

  • Minimum of p(t) occurs when cos(2ωt − 30°) = +1 ⇒ pmin = 2300(0.8660 − 1) = −308.2 W < 0. So p(t) is negative for part of the cycle; energy flows momentarily back to the source due to reactive component.

Answer: (a) p(t) = 2300[0.8660 − cos(2ωt − 30°)] W; (b) average P = 1991.8 W; (c) yes, p(t) goes negative momentarily since φ ≠ 0.

Common mistakes

  • Forgetting that PF = cosφ only for sinusoidal waveforms; in presence of harmonics, PF < cos(displacement angle).
  • Mixing line and phase values in three-phase formulas (e.g., using VL with Iphase); stick consistently to line quantities for P = √3·VL·IL·cosφ in balanced loads.
  • Sign of reactive power: inductive loads have +Q and lagging PF; capacitive loads have −Q and leading PF. Drawing Q downward for capacitive in the power triangle helps remember.
  • In two-wattmeter method, not anticipating a negative reading when φ > 60° lagging; the instrument may need reversal of coil connections for upscale reading.
  • For PF correction, using Vphase instead of VL (or vice versa) when sizing three-phase capacitor banks; use Qc(Y) with Vph and Qc(Δ) with VL as defined.
  • Computing capacitor size with f instead of ω = 2πf in C = Qc/(ωV²); this gives a value that is 2π times wrong.

For your exam

  • Numericals: Single-phase and three-phase problems—given P and PF, find I, S, Q; size capacitors for PF correction; compute two-wattmeter readings and infer PF; convert between star/delta capacitor bank ratings.
  • Diagrams: Power triangle with P, Q, S and angle φ; phasor diagram showing V and I with lag/lead; two-wattmeter connection schematic (name coils and line-to-line voltages). Label axes and quantities carefully.
  • Full-marks answers include: correct formula before substitution, correct units throughout, a neat labeled diagram where asked, a short sentence interpreting the result (e.g., “PF improves from 0.70 lag to 0.95 lag; line current reduces from 31.06 A to 22.88 A”).

Quick check

  1. A single-phase 230 V load draws 10 A at 0.6 lag PF. Find P, Q, and S.
  2. In a three-phase balanced system at 415 V line, IL = 20 A, PF = 0.9 lag. Find P and Q.
  3. Two-wattmeter readings are W1 = 5 kW, W2 = 2 kW. Find total P and PF (assume balanced, lagging).

Answers: 1) S = V·I = 2300 VA; P = S·PF = 1380 W; Q = √(S² − P²) = 1840 var (or P·tanφ with φ ≈ 53.13° gives 1840 var). 2) P = √3·VL·IL·cosφ = 1.732·415·20·0.9 ≈ 12.95 kW; Q = √3·VL·IL·sinφ with sinφ ≈ 0.4359 ⇒ Q ≈ 6.27 kVAr. 3) P = W1 + W2 = 7 kW; tanφ = √3(W1 − W2)/(W1 + W2) = 1.732·3/7 ≈ 0.742 ⇒ PF = cosφ ≈ 0.80 lag.