Three-phase circuits

Star and delta connections, line and phase relations, balanced three-phase power and the two-wattmeter method, with star-versus-delta and two-wattmeter worked examples.

Drafted with Aria, reviewed by the AiCanCode.org team · Updated . How we write and check our notes. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Almost every industrial motor, CNC machine, compressor and VFD in a plant runs from a three-phase supply (400 V line-to-line, 50 Hz in India). Three-phase systems deliver constant instantaneous power, need less conductor material than single-phase for the same power, and produce the rotating magnetic field that makes induction motors self-starting. Reading a motor nameplate, sizing a cable or wiring a star-delta starter all need the relations in this topic.

Key ideas

Generating three phases. Three identical windings spaced 120° apart on a generator produce three EMFs of equal magnitude displaced by 120° in time. With phase sequence R-Y-B (also called A-B-C or positive sequence): V_R = V∠0°, V_Y = V∠−120°, V_B = V∠+120°. In a balanced set the three phasors sum to zero at every instant. Reversing any two supply lines reverses the sequence, which reverses the direction of rotation of a three-phase motor.

Star (wye, Y) connection. One end of each phase is joined at a neutral point N.

  • Phase voltage V_ph is measured from line to neutral; line voltage V_L is between two lines.
  • V_L = √3·V_ph, and each line voltage leads the corresponding phase voltage by 30° (for positive sequence).
  • Line current equals phase current: I_L = I_ph.
  • A neutral wire (4-wire system) carries the phasor sum of the line currents: zero for a balanced load, non-zero for an unbalanced one. Domestic single-phase 230 V supplies are one phase plus neutral of a 400 V star system.

Delta (mesh, Δ) connection. The three phases are connected end to end in a closed loop; there is no neutral.

  • V_L = V_ph.
  • I_L = √3·I_ph, and each line current lags the corresponding phase current by 30° (positive sequence).

Balanced loads. When all three phase impedances are equal, analyse one phase (the "per-phase equivalent") and multiply power by three. A delta load can be converted to an equivalent star with Z_Y = Z_Δ/3. The phase angle φ in the power formulas is always the angle between phase voltage and phase current (the angle of the load impedance), not between line quantities.

Power. Total power is the same expression for star and delta: P = √3·V_L·I_L·cos φ. For a balanced system the instantaneous total power is constant (no pulsation at 2f), which gives smooth motor torque.

Star versus delta for the same impedance. Connecting the same three impedances in delta instead of star, on the same line voltage, triples the power and the line current. A star-delta starter uses this: it starts the motor in star (one-third of the delta starting current and torque) and switches to delta to run.

Measuring power: two-wattmeter method. In a three-wire system (balanced or unbalanced), two wattmeters with current coils in two lines and pressure coils from those lines to the third line read a total equal to the three-phase power. For a balanced load W1 = V_L·I_L·cos(30° − φ) and W2 = V_L·I_L·cos(30° + φ) (lagging φ). Consequences:

  • At unity pf both read equal.
  • At pf = 0.5 (φ = 60°) one wattmeter reads zero.
  • Below pf 0.5 one reading goes negative (reverse its current coil and subtract).

Unbalanced loads. With an unbalanced star load and no neutral, the star point shifts away from the supply neutral (neutral shift), and the phase voltages are no longer equal; solve with nodal analysis (Millman's theorem). This is why single-phase loads in a building must be spread across the three phases.

Formulas

V_L = √3 · V_ph; I_L = I_ph (star) V_L = V_ph; I_L = √3 · I_ph (delta)

  • V_L: line-to-line RMS voltage (V); V_ph: phase RMS voltage (V); I_L, I_ph: RMS currents (A).

I_ph = V_ph / |Z_ph|; cos φ = R_ph / |Z_ph|

  • Z_ph: per-phase impedance (Ω); φ: angle of Z_ph.

P = 3·V_ph·I_ph·cos φ = √3·V_L·I_L·cos φ (W) Q = √3·V_L·I_L·sin φ (VAR) S = √3·V_L·I_L (VA)

  • Valid for balanced loads, star or delta.

Z_Y = Z_Δ / 3 (balanced delta-to-star conversion)

P = W1 + W2; Q = √3·(W1 − W2); tan φ = √3·(W1 − W2) / (W1 + W2)

  • Two-wattmeter method; the Q and tan φ relations hold for a balanced load and sinusoidal supply; W1 is the larger reading for a lagging load.

Worked examples

Example 1 (standard: star and delta load). Three identical impedances Z = 8 + j6 Ω are connected to a 400 V, 50 Hz three-phase supply. Find line current and total power (a) in star, (b) in delta.

  1. |Z| = √(8² + 6²) = 10 Ω; cos φ = 8/10 = 0.8 lagging.
  2. (a) Star: V_ph = V_L/√3 = 400/1.732 = 230.9 V.
  3. I_ph = I_L = 230.9/10 = 23.09 A.
  4. P = 3·I_ph²·R = 3 × 23.09² × 8 = 12 800 W. Check: √3 × 400 × 23.09 × 0.8 = 12 800 W.
  5. (b) Delta: V_ph = 400 V, I_ph = 400/10 = 40 A, I_L = √3 × 40 = 69.28 A.
  6. P = 3 × 40² × 8 = 38 400 W.

Star: I_L = 23.1 A, P = 12.8 kW. Delta: I_L = 69.3 A, P = 38.4 kW (three times the star value).

Example 2 (GATE level: two-wattmeter method). A balanced three-phase induction motor on a 400 V supply is tested with two wattmeters reading W1 = 8 kW and W2 = 4 kW. Find the total power, power factor, reactive power and line current.

  1. P = W1 + W2 = 8 + 4 = 12 kW.
  2. tan φ = √3·(W1 − W2)/(W1 + W2) = 1.732 × 4/12 = 0.5774, so φ = 30.0°.
  3. pf = cos 30° = 0.866 lagging (motor load).
  4. Q = √3·(W1 − W2) = 1.732 × 4 = 6.93 kVAR.
  5. I_L = P/(√3·V_L·cos φ) = 12 000/(1.732 × 400 × 0.866) = 20.0 A.

P = 12 kW, pf = 0.866 lagging, Q = 6.93 kVAR, I_L = 20.0 A.

Common mistakes

  • Using line voltage directly as phase voltage in a star load (forgetting the √3).
  • Taking φ as the angle between line voltage and line current; it is the phase-impedance angle.
  • Writing P = 3·V_L·I_L·cos φ (it is √3 with line values, 3 with phase values).
  • Expecting the neutral current to be non-zero in a balanced load.
  • Discarding a negative wattmeter reading instead of subtracting it when pf < 0.5.
  • Assuming phase voltages stay equal in an unbalanced star load without a neutral.

For GATE ME

Questions are usually short numericals: line and phase currents for balanced star or delta loads, total power, star-delta conversion, effect of changing connection on power or starting current, and pf from two wattmeter readings. Practise the per-phase approach and the two-wattmeter formulas until they are automatic.

Quick check

  1. A star-connected supply has 230 V phase voltage. What is the line voltage?
  2. In a delta load the phase current is 10 A. What is the line current?
  3. Two wattmeters read equal values on a balanced load. What is the power factor?
  4. One wattmeter reads zero on a balanced load. What is the power factor?
  5. The same three resistors are reconnected from star to delta on the same supply. By what factor does the power change?

Answers: 1. 398 V (nominally 400 V). 2. 17.3 A. 3. Unity. 4. 0.5. 5. It triples.

Try answering each one aloud before you open it.

  1. 1.What is the relation between line and phase quantities in star and delta connections?Concept

    In star, line current equals phase current and line voltage is √3 times phase voltage, leading it by 30° in a positive (RYB) sequence. In delta, line voltage equals phase voltage and line current is √3 times phase current, lagging it by 30°. Total power is √3·V_L·I_L·cos φ in both, where φ is the angle of the phase impedance.

  2. 2.Why is three-phase power preferred over single-phase for transmission and motors?Concept

    For the same power and voltage, three-phase needs less conductor material — about 75% of a single-phase line. In a balanced system the instantaneous power is constant rather than pulsing at twice the supply frequency, so motors run smoothly with steady torque. Three-phase windings also produce a rotating magnetic field directly, so induction motors are self-starting.

  3. 3.How does the two-wattmeter method measure three-phase power, and what does a negative reading mean?Concept

    Two wattmeters have their current coils in two lines and their pressure coils from those lines to the third; by Blondel's theorem their sum is the total power for any three-wire load, balanced or not. For a balanced load, √3 times the difference gives the reactive power, and from the two you get tan φ. A negative reading — read after reversing that meter's current coil — means the power factor is below 0.5.

  4. 4.What is the role of the neutral in a star-connected system, and what happens if it breaks with an unbalanced load?Concept

    The neutral carries the difference current of the three phases and holds the star point at earth potential, so each load sees its own phase voltage. If the neutral opens with an unbalanced load, the star point shifts: lightly loaded phases see higher voltage and heavily loaded ones lower, which can burn out single-phase equipment. That is why the neutral is never fused in distribution.

  5. 5.Why does a star-delta starter reduce the starting current of an induction motor, and by how much?Concept

    At start the winding is connected in star, so each phase gets V_L/√3 instead of V_L. Phase current falls by √3, and because the line current in delta is √3 times phase current, the line current drawn in star is one-third of what direct-on-line delta starting would draw. Starting torque, proportional to voltage squared, also falls to one-third.

  6. 6.What is phase sequence and why does it matter?Concept

    Phase sequence is the order in which the three phase voltages reach their peaks, for example R-Y-B. Swapping any two supply lines reverses it, which reverses the direction of an induction motor's rotating field and so its rotation. It also matters when paralleling generators or transformers and when connecting energy meters or protection relays — a wrong sequence gives wrong readings or a fault.

Finished this topic? Mark it so your progress, study plan and readiness keep up.

Stuck on something here?