Measurement of power and wattmeters

Electrodynamometer wattmeter, its connection and pressure-coil inductance errors, LPF wattmeters, Blondel's theorem and the two-wattmeter method for three-phase power and power factor.

Drafted with Aria, reviewed by the AiCanCode.org team. Spotted an error? Use Give Feedback at the bottom of the page.

Why it matters

Power, not volt-amperes, is what a load converts into heat, motion or light, and what efficiency and loss tests depend on. On AC the product V × I overstates power whenever current and voltage are out of phase, so a wattmeter — or the two-wattmeter method on three-phase supplies — is needed. Transformer and motor tests, energy audits and every three-phase lab use these methods.

Key ideas

Power quantities. For sinusoidal V and I with phase angle φ:

  • Active power P = VI cos φ (W).
  • Reactive power Q = VI sin φ (var).
  • Apparent power S = VI (VA), with S² = P² + Q².
  • Power factor = cos φ = P/S.

Electrodynamometer wattmeter.

  • Fixed current coil (CC), a few thick turns, in series with the load.
  • Moving pressure (potential) coil (PC), many fine turns with a large series non-inductive resistance, connected across the supply.
  • The instantaneous torque is proportional to v·i, and the moving system responds to its average, so the deflection is proportional to VI cos φ, the true power, for any waveform (to the extent the PC current stays in phase with V). It works on DC and AC and has a nearly uniform scale.
  • Air damping, spring control.
  • Wattmeter ranges are set by current and voltage ratings as well as the power scale; an instrument can be overloaded at low power factor without the pointer going off scale, so always watch an ammeter and voltmeter too.

Errors in a wattmeter.

  • Connection (loss) error: with the PC on the supply side it also measures the CC's I²R loss; with the PC on the load side the CC also carries the PC current and the meter reads the PC loss V²/Rp. Use the first for high current/low voltage loads and the second otherwise, or fit a compensating coil — a winding in series with the PC, wound with the CC, that cancels the field of the PC current.
  • Pressure-coil inductance error: the PC current lags V by β = tan⁻¹(ωL/Rp). On lagging loads the meter reads high, and the error grows sharply at low power factor. It is reduced by a capacitor across part of the series resistance.
  • Eddy currents in metal parts, stray fields (shielding), and temperature.
  • Low power factor (LPF) wattmeters have a compensated PC, a low-inductance PC circuit and a strong torque so that full-scale deflection corresponds to a power factor of 0.1 or 0.2.

Three-phase power.

  • Blondel's theorem: in an n-wire system, n − 1 wattmeters give the total power, each with its CC in one line and its PC between that line and the common line.
  • Three-wattmeter method (4-wire star): total power is the sum of the three readings.
  • Two-wattmeter method (any 3-wire load, balanced or not, star or delta): P = W1 + W2.
    • For a balanced load with sinusoidal supply, W1 = VL·IL·cos(30° − φ) and W2 = VL·IL·cos(30° + φ). The readings also give φ.
    • At unity pf both are equal; at pf = 0.5 one reads zero; below 0.5 one reads negative — reverse its PC (or CC) to get an up-scale reading and subtract it.
  • One-wattmeter method works only for balanced loads (PC between a line and a star point; total = 3 × reading).
  • Reactive power with one wattmeter: CC in line 1, PC across lines 2–3; reading = VL·IL·sin φ, total Q = √3 × reading (balanced load).

Formulas

P = V·I·cos φ ; Q = V·I·sin φ ; S = V·I ; S² = P² + Q² V, I = RMS values (V, A); φ = angle by which I lags V.

True power = Reading × cos φ / (cos β · cos(φ − β)) ; β = tan⁻¹(ωL/Rp) L = PC inductance (H); Rp = total PC circuit resistance (Ω). For lagging load.

P = √3·VL·IL·cos φ (balanced three-phase) W1 = VL·IL·cos(30° − φ) ; W2 = VL·IL·cos(30° + φ) (two-wattmeter, balanced) P = W1 + W2 ; Q = √3·(W1 − W2) ; tan φ = √3·(W1 − W2) / (W1 + W2) VL = line voltage (V); IL = line current (A); W1 = the larger reading on a lagging load.

Worked examples

Example 1 — pressure-coil inductance error. A wattmeter's pressure-coil circuit has Rp = 1000 Ω and L = 20 mH. It measures a load of 230 V, 10 A at power factor 0.1 lagging (50 Hz). Find the reading and the percentage error.

  1. β = tan⁻¹(2π × 50 × 0.020 / 1000) = tan⁻¹(0.006283) = 0.360°.
  2. φ = cos⁻¹(0.1) = 84.26°; φ − β = 83.90°.
  3. Correction factor cos β·cos(φ − β)/cos φ = 1.0625.
  4. True power = 230 × 10 × 0.1 = 230 W; reading = 230 × 1.0625 = 244.4 W.

Answer: the meter reads about 244 W, 6.25 % high — a small β gives a big error at low power factor, which is why LPF wattmeters are compensated.

Example 2 — two-wattmeter method (GATE level). A balanced three-phase load on a 400 V supply gives W1 = 2000 W and W2 = 1000 W. Find (a) total power, (b) power factor, (c) line current, (d) the readings if the same current flowed at pf 0.4 lagging.

  1. P = 2000 + 1000 = 3000 W.
  2. tan φ = √3 × (2000 − 1000)/3000 = 0.5774 → φ = 30°, pf = 0.866 lagging.
  3. IL = P/(√3·VL·cos φ) = 3000/(1.732 × 400 × 0.866) = 5.0 A.
  4. At pf 0.4 with IL = 5 A: φ = 66.42°. W1 = 400 × 5 × cos(−36.42°) = 1609 W; W2 = 400 × 5 × cos(96.42°) = −224 W.

Answer: (a) 3 kW; (b) 0.866 lagging; (c) 5.0 A; (d) W1 ≈ 1609 W, W2 ≈ −224 W (total 1386 W = √3 × 400 × 5 × 0.4).

Common mistakes

  • Taking V × I as power on AC; it is apparent power in VA.
  • Adding the two wattmeter readings when one has been reversed: the reversed reading must be subtracted.
  • Using the balanced-load readings W1 = VL·IL·cos(30° ∓ φ) for an unbalanced load; only P = W1 + W2 holds in general.
  • Using the two-wattmeter method on a 4-wire system with neutral current; Blondel's theorem needs three meters.
  • Ignoring the current and voltage ratings of a wattmeter — at low pf the CC can be overloaded while the power reading is small.
  • Forgetting that PC inductance makes a lagging-load reading high (and a leading-load reading low).

For GATE IN

Expect NAT questions on two-wattmeter readings (power, power factor, negative reading at pf below 0.5), reactive power from one wattmeter, and error due to PC inductance or connection. MCQs test Blondel's theorem, compensating coils and LPF wattmeters. Practise converting between W1, W2, φ and line current quickly, and watch for leading loads, where W1 and W2 swap roles.

Quick check

  1. Two-wattmeter readings are equal and positive. What is the power factor?
  2. One reading is zero. Power factor?
  3. With a balanced load, W1 = 5 kW and W2 = 1 kW. Power factor?
  4. A one-wattmeter reactive-power connection reads 1.2 kW. Total reactive power? Answers: 1. unity; 2. 0.5; 3. tan φ = √3 × 4/6 = 1.155, φ = 49.1°, pf = 0.655; 4. √3 × 1.2 = 2.08 kvar.

Try answering each one aloud before you open it.

  1. 1.What is a wattmeter and what is its primary function?Concept

    A wattmeter is an instrument used to measure the power in an electrical circuit. Its primary function is to measure the real power (in watts) consumed by a load in an AC or DC circuit. It typically consists of a current coil and a voltage coil, which work together to provide a reading proportional to the power being consumed.

  2. 2.Explain the working principle of an electrodynamometer wattmeter.Concept

    An electrodynamometer wattmeter operates on the principle of the interaction between the magnetic fields of fixed and moving coils. The fixed coil, known as the current coil, carries the load current, while the moving coil, known as the voltage coil, carries a current proportional to the voltage across the load. The interaction between these magnetic fields produces a deflecting torque proportional to the power in the circuit, which is indicated on the scale.

  3. 3.Why is a wattmeter used in power measurement instead of just using a voltmeter and ammeter?Application

    A wattmeter is used because it directly measures real power, which is the actual power consumed by the load. Using a voltmeter and ammeter separately would only provide apparent power (in VA), which includes both real power and reactive power. The wattmeter accounts for the phase difference between voltage and current, providing a more accurate measurement of power consumption.

  4. 4.What happens if the current coil and voltage coil of a wattmeter are interchanged?Application

    If the current coil and voltage coil of a wattmeter are interchanged, the wattmeter will not function correctly. The current coil is designed to handle higher currents and has lower resistance, while the voltage coil is designed for higher voltage with higher resistance. Interchanging them could lead to inaccurate readings and potential damage to the instrument due to overloading.

  5. 5.Explain the significance of the power factor in the measurement of power using a wattmeter.Concept

    The power factor is significant because it represents the phase difference between voltage and current in an AC circuit. A wattmeter measures real power, which is the product of voltage, current, and the cosine of the phase angle (power factor). A low power factor indicates that more current is needed to deliver the same amount of real power, which can lead to inefficiencies and higher losses in the system.

  6. 6.How is power measured in a three-phase system with wattmeters?Concept

    By Blondel's theorem an n-wire system needs n − 1 wattmeters, so a 3-wire system (star without neutral, or delta) needs two: each has its current coil in one line and its pressure coil between that line and the third line. The total power is W1 + W2 for any load, balanced or unbalanced. For a balanced load the readings also give the power factor, tan φ = √3(W1 − W2)/(W1 + W2); below pf 0.5 one meter reads negative and must be reversed and subtracted. A 4-wire system with neutral current needs three wattmeters.

  7. 7.What is the effect of power factor on the reading of a wattmeter in an inductive load?Application

    In an inductive load, the power factor is typically less than one, meaning there is a phase difference between voltage and current. The wattmeter reading will be lower than the apparent power because it measures real power, which is the product of voltage, current, and the power factor. As the power factor decreases, the wattmeter reading decreases, indicating less real power is being consumed.

  8. 8.Calculate the power measured by a wattmeter if the voltage across the load is 230 V, the current through the load is 5 A, and the power factor is 0.8.Numerical

    The power measured by the wattmeter can be calculated using the formula: P = V × I × cos(φ), where V is the voltage, I is the current, and cos(φ) is the power factor. Substituting the given values: P = 230 V × 5 A × 0.8 = 920 W. Therefore, the power measured by the wattmeter is 920 watts.

  9. 9.What are the main errors of an electrodynamometer wattmeter and how are they reduced?Application

    Connection error: the meter includes either the current-coil loss or the pressure-coil loss depending on which side the pressure coil is connected; a compensating coil in series with the pressure coil cancels the latter. Pressure-coil inductance makes the PC current lag the voltage by a small angle β, so the meter reads high on lagging loads, badly so at low power factor; a capacitor across part of the series resistance compensates it. Stray fields, eddy currents and temperature also cause error, reduced by shielding, non-metallic parts and low-temperature-coefficient resistors.

Finished this topic? Mark it so your progress, study plan and readiness keep up.

Stuck on something here?