Instrument transformers: CT and PT
Current and potential transformers: connection, burden, why a CT secondary must never be opened, ratio and phase-angle errors with the CT phasor formulas, turns compensation and power measurement through instrument transformers.
Drafted with Aria, reviewed by the AiCanCode.org team. Spotted an error? Use Give Feedback at the bottom of the page.
Why it matters
You cannot connect a 5 A ammeter to a 2000 A busbar or a 110 V voltmeter to an 11 kV line. Current transformers (CTs) and potential (voltage) transformers (PTs) scale these down and isolate the instruments and relays from the high-voltage circuit. Their ratio and phase-angle errors decide whether a tariff meter bills correctly and whether a relay trips when it should.
Key ideas
Purpose. Instrument transformers extend AC meter ranges, isolate low-voltage instruments from the power circuit, and allow standard instruments (5 A or 1 A, 110 V) to be used everywhere. Measurements multiply the instrument reading by the transformer ratio.
Current transformer.
- The primary is in series with the line: a few turns, or a single bar (bar-primary CT). The secondary has many turns and feeds ammeters, wattmeter current coils and relays — a very low-impedance burden, so the CT works almost short-circuited.
- The primary current is set by the external circuit, not by the CT burden. The core flux is small because the secondary ampere-turns nearly cancel the primary ampere-turns.
- Never open-circuit a CT secondary while the primary carries current. With no secondary ampere-turns to oppose it, the whole primary MMF magnetises the core: flux rises to saturation, a dangerously high peak voltage appears across the open secondary, the core overheats, and it may be left with residual magnetism that changes its ratio. Short the secondary with the shorting link before removing an instrument.
Potential transformer.
- The primary is connected in parallel (across the line), the secondary feeds voltmeters, wattmeter pressure coils and relays — a high-impedance burden, so it works like a lightly loaded power transformer.
- A PT secondary must never be short-circuited (fuses are fitted). One end of the secondary is earthed for safety.
Errors. Because some primary current is needed to magnetise the core and supply core loss, and because of winding resistance and leakage reactance, the actual ratio is not exactly the turns ratio and the secondary quantity is not exactly 180° (reversed) from the primary.
- Ratio error: difference between the nominal ratio Kn (marked on the nameplate, e.g. 1000/5) and the actual ratio R = Ip/Is (or Vp/Vs).
- Phase-angle error θ: the angle between the primary phasor and the reversed secondary phasor; positive when the reversed secondary leads. It does not matter for ammeters or voltmeters but causes errors in wattmeters, energy meters and directional relays, especially at low power factor.
- CT errors grow with burden (larger secondary voltage needs more flux and more exciting current) and at low primary current. Reduced by low-loss, high-permeability cores (CRGO, nickel-iron), short magnetic paths, and turns compensation (one or two secondary turns fewer than nominal).
- PT errors grow with burden (more voltage drop in the windings). Reduced by low winding resistance and reactance and a well-designed core.
- Burden is the load on the secondary, in VA at rated secondary current or voltage, with its power factor. Accuracy class (e.g. 0.2, 0.5, 1 for metering; 5P, 10P for protection) defines permissible ratio and phase errors — take the limits from the relevant standard.
Metering versus protection CTs. Metering CTs must be accurate near rated current and should saturate during faults to protect the instruments; protection CTs must stay reasonably accurate up to many times rated current (accuracy-limit factor).
Formulas
Kn = rated primary / rated secondary (e.g. 1000/5 = 200)
R = Ip / Is (CT) ; R = Vp / Vs (PT) — actual ratio
Ratio error (%) = (Kn − R) / R × 100
Ip = R·Is ; Vp = R·Vs ; corrected primary from the reading.
R ≈ n + (Im·sin δ + Iw·cos δ) / Is (CT)
θ ≈ (Im·cos δ − Iw·sin δ) / (n·Is) rad (CT; × 180/π for degrees)
n = turns ratio Ns/Np; Is = secondary current (A); Im, Iw = magnetising and core-loss components of the exciting current referred to the primary (A); δ = phase angle of the secondary burden (lagging positive).
Primary power = wattmeter reading × CT ratio × PT ratio (neglecting phase-angle errors)
Worked examples
Example 1 — CT errors. A bar-primary CT has 200 secondary turns (nominal ratio 1000/5 = 200). At rated current the secondary burden has a power factor of 0.8 lagging. Referred to the primary, the magnetising component is 2 A and the core-loss component 1 A. Find the actual ratio, ratio error and phase-angle error.
n = 200/1 = 200;cos δ = 0.8,sin δ = 0.6.R = 200 + (2 × 0.6 + 1 × 0.8)/5 = 200 + 2.0/5 = 200.4.Ratio error = (200 − 200.4)/200.4 × 100 = −0.20 %.θ = (2 × 0.8 − 1 × 0.6)/(200 × 5) = 1.0/1000 = 0.001 rad = 0.0573° = 3.4 minutes.
Answer: R = 200.4, ratio error −0.20 % (the meter reads low), phase-angle error ≈ 3.4′.
Example 2 — turns compensation (GATE level). The CT of Example 1 has its secondary reduced to 199 turns, with the same excitation components and burden. Find the new ratio error.
n = 199;R = 199 + 0.4 = 199.4.Ratio error = (200 − 199.4)/199.4 × 100 = +0.30 %.
Answer: +0.30 %. One turn over-corrects at this burden; in practice the compensation is chosen so that the error stays smallest over the working range of current and burden.
Example 3 — power through instrument transformers. A wattmeter connected through a 100/5 A CT and an 11 000/110 V PT reads 400 W. Neglecting errors, find the primary power.
- CT ratio
= 20; PT ratio= 100. P = 400 × 20 × 100 = 800 000 W.
Answer: 800 kW.
Common mistakes
- Treating the CT ratio 1000/5 as a turns ratio Np:Ns of 1000:5 — the turns ratio is the inverse of the current ratio (Ns/Np ≈ 200).
- Opening the CT secondary to remove an ammeter; always short it first.
- Short-circuiting a PT secondary.
- Defining ratio error with the actual ratio in the numerator (sign comes out wrong).
- Ignoring phase-angle error in power measurement at low power factor — a few minutes of arc matter when cos φ is small.
- Assuming CT error is constant; it rises with burden and at low current.
For GATE IN
Expect NAT questions on actual ratio, ratio error and phase-angle error from excitation components and burden power factor, turns compensation, and primary power from a reading through CT and PT. MCQs test why a CT secondary must not be open-circuited, burden and accuracy class, and metering versus protection CTs. Practise the CT phasor diagram until the formulas are obvious.
Quick check
- A 200/5 A CT feeds an ammeter reading 3.5 A. Primary current?
- What happens if a loaded CT's secondary is opened?
- Nominal ratio 400, actual ratio 402. Ratio error?
- Is a CT's burden a high or a low impedance? Answers: 1. 140 A; 2. the core saturates, a dangerous high voltage appears across the secondary and the core overheats; 3. (400 − 402)/402 = −0.50 %; 4. low impedance (the CT works almost short-circuited).
Interview questions
All Electrical and Electronic Measurements interview questionsTry answering each one aloud before you open it.
1.What is a Current Transformer (CT) and what is its primary function?Concept
A Current Transformer (CT) is an instrument transformer used to measure alternating current (AC). Its primary function is to reduce high current levels to a lower, manageable value for measurement and protection purposes. This allows for safe monitoring and control of electrical systems without directly exposing measurement devices to high currents.
2.What is a Potential Transformer (PT) and what is its primary function?Concept
A Potential Transformer (PT), also known as a Voltage Transformer, is an instrument transformer used to step down high voltage levels to a lower, standardized value for measurement and protection. This enables the safe measurement of high voltages by standard low-voltage instruments.
3.Explain the difference between a CT and a PT.Concept
The main difference between a CT and a PT is their function and application. A CT is used to measure current by stepping down high current levels, while a PT is used to measure voltage by stepping down high voltage levels. CTs are connected in series with the circuit, whereas PTs are connected in parallel.
4.Why are CTs and PTs used in power systems?Application
CTs and PTs are used in power systems to safely measure high currents and voltages. They provide isolation between high voltage circuits and measurement devices, ensuring safety and accuracy. This is crucial for monitoring, control, and protection of electrical systems.
5.What happens if a CT is open-circuited while in operation?Application
If a CT is open-circuited while in operation, it can produce dangerously high voltages across its secondary terminals. This can damage the CT and pose a safety hazard. Therefore, CTs should always be short-circuited or connected to a burden when in operation.
6.What precautions apply when connecting a potential transformer?Application
The PT primary goes across the line (in parallel) and its secondary feeds high-impedance burdens such as voltmeters and pressure coils. The secondary must never be short-circuited, so it is protected by fuses, and one end of the secondary is earthed so that a primary-to-secondary insulation failure cannot make the instruments live. Polarity marks must be respected for wattmeters, energy meters and directional relays, and the connected burden must stay within the rated VA or the ratio and phase errors exceed the accuracy class.
7.How does the burden of a CT affect its performance?Application
The burden of a CT, which is the load connected to its secondary, affects its accuracy and performance. A higher burden can lead to increased errors in current measurement. CTs are designed to operate within a specific burden range to maintain accuracy.
8.A 100/5 A current transformer carries a primary current of 60 A. What is the secondary current?Numerical
The nominal ratio is 100/5 = 20, so the secondary current is 60/20 = 3 A, ignoring the small ratio error. Note that 100/5 is the current ratio; the turns ratio Ns/Np is about 20, the inverse of the current ratio expressed as Np:Ns.
9.A PT has a primary voltage of 11 kV and a turns ratio of 110:1. What is the secondary voltage?Numerical
The secondary voltage (V_s) can be calculated using the formula: V_s = (Primary Voltage / Turns Ratio) = 11,000 V / 110 = 100 V.
10.Explain why CTs are rated in terms of burden and accuracy class.Concept
CTs are rated in terms of burden and accuracy class to ensure they operate within specified limits for accurate current measurement. The burden rating indicates the maximum load the CT can handle without exceeding its accuracy limits. The accuracy class defines the permissible error at rated conditions, ensuring reliable performance in protection and measurement applications.
Finished this topic? Mark it so your progress, study plan and readiness keep up.
Stuck on something here?