Electrical Machines — formula sheet
Instrumentation Engineering · GATE IN · SI units. Drafted with Aria, checked by the AiCanCode.org team.
Magnetic Circuits and Electromechanical Energy Conversion
F = N·I— Magnetomotive force in ampere-turns (At); N turns, I current (A).Φ = B·A— Flux (Wb); B flux density (T), A area (m²), uniform field.B = μ0·μr·H ; μ0 = 4π × 10⁻⁷ H/m— flux density from field intensity H (A/m); valid below saturation.R = l / (μ0·μr·A) ; Φ = F / ΣR— Reluctance (At/Wb) of a path of length l (m); series reluctances add.L = N² / R = N·Φ / I— Inductance (H) of a linear magnetic circuit.W = ½·L·I² ; w = B² / (2μ0)— Stored energy (J) and energy density in air (J/m³).F_pull = B²·A / (2μ0)— Force (N) on one pole face of area A (m²) across an air gap.T = ½·I²·dL/dθ— Reluctance torque (N·m), linear system, constant current.e = B·l·v ; F = B·I·l— Motional EMF (V) and force on a conductor (N); B, l, v mutually perpendicular.
Single-phase Transformer: Construction and Equivalent Circuit
E = 4.44·f·N·Φm— rms induced EMF (V); f (Hz), N turns, Φm peak flux (Wb).a = N1/N2 = E1/E2 ≈ V1/V2 = I2/I1— Turns ratio; currents are in inverse ratio of turns.Z' = a²·Z— Impedance referred from secondary to primary (Ω).R01 = R1 + a²·R2 ; X01 = X1 + a²·X2— Equivalent resistance and reactance referred to primary (Ω); divide by a² to refer to secondary.I0 = √(Iw² + Iμ²) ; Iw = I0·cos φ0 ; Iμ = I0·sin φ0— No-load current and its core-loss and magnetising components (A).
Transformer Phasor Diagram, Regulation and Efficiency
ε ≈ %R·cos φ ± %X·sin φ— Percent regulation; + lagging, − leading; %R = I·R02/V2 × 100, %X = I·X02/V2 × 100.Regulation = (V20 − V2) / V2 × 100 %— Definition with full-load (rated) voltage V2 as base.ε_max = %Z at cos φ = R/Z (lagging) ; ε = 0 at cos φ = X/Z (leading).η = x·S·cos φ / (x·S·cos φ + Pi + x²·Pcu,FL)— Efficiency at fraction x of rated S (VA); Pi core loss, Pcu,FL full-load copper loss (W).x_ηmax = √(Pi / Pcu,FL)— Load fraction at maximum efficiency (copper loss = core loss).η_all-day = output energy (24 h) / input energy (24 h).
Open-circuit and Short-circuit Tests
cos φ0 = W0 / (V0·I0) ; R0 = V0/Iw ; X0 = V0/Iμ— OC test (usually LV side, rated voltage); W0 = core loss.Z01 = Vsc/Isc ; R01 = Wsc/Isc² ; X01 = √(Z01² − R01²)— SC test (usually HV side, rated current); Wsc = copper loss at Isc.Pcu,FL = Wsc·(I_rated / Isc)²— Full-load copper loss from an SC test at a different current.
Autotransformer and Instrument Transformers
k = V_LV / V_HV— Autotransformer ratio (< 1).I_common = I_LV − I_HV— Current in the common winding (A).S_conductive = k·S ; S_inductive = (1 − k)·S— Power transferred conductively and inductively (step-down, S = load VA).Cu_auto / Cu_2-winding = 1 − k— Copper saving = k.S_auto = S_2w·(V_HV / V_series)— Rating when a two-winding transformer is reconnected as an autotransformer.Ratio error = (Kn·Is − Ip) / Ip × 100 %— CT (PT similarly with voltages); Kn = nominal ratio, e.g. 200/5.
DC Generator: Construction, EMF Equation and Characteristics
E = P·Φ·Z·N / (60·A)— Generated EMF (V); P poles, Φ flux per pole (Wb), Z armature conductors, N (rpm), A parallel paths (A = P lap, A = 2 wave).E = V + Ia·Ra + V_brush— Generator voltage equation.Ia = IL + Ish ; Ish = V / Rsh— Shunt generator currents (A).E ∝ Φ·N— Same machine at two operating points.
DC Motor: Torque Equation, Characteristics and Starting
V = Eb + Ia·Ra— Motor voltage equation; Eb back EMF (V).T = Ka·Φ·Ia ; Ka = P·Z / (2π·A)— Electromagnetic torque (N·m).T = Eb·Ia / ω = 9.55·Eb·Ia / N— Torque from developed power; ω (rad/s), N (rpm).Shunt: T ∝ Ia ; Series (unsaturated): T ∝ Ia², N ∝ Eb / Ia.R_start = V / I_start − Ra— External starting resistance (Ω).
Speed Control of DC Motors
N ∝ (V − Ia·Ra) / Φ— Speed equation.N2/N1 = [(V2 − Ia2·Ra) / (V1 − Ia1·Ra)]·(Φ1/Φ2)— Ratio between two operating points.Ia2 = Ia1·(Φ1/Φ2)— Armature current after a flux change at constant load torque.Armature voltage control: constant torque (below base speed) ; field control: constant power (above base speed).
Three-phase Induction Motor: Principle and Equivalent Circuit
Ns = 120·f / P ; s = (Ns − N) / Ns— Synchronous speed (rpm) and slip.f2 = s·f ; E2s = s·E2 ; X2s = s·X2— Rotor frequency (Hz), EMF and reactance at slip s.I2 = E2 / √((R2/s)² + X2²)— Rotor current per phase (A).Pag : Pcu2 : Pm = 1 : s : (1 − s)— Air-gap power, rotor copper loss, gross mechanical power.T = Pag / ωs = Pm / ωr— Electromagnetic torque (N·m); ωs = 2π·Ns/60.
Torque-slip Characteristics of Induction Motors
T = 3·V1²·(R2'/s) / {ωs·[(R1 + R2'/s)² + X²]}— Torque (N·m); V1 per-phase voltage, X = X1 + X2'.T ∝ s·E2²·R2 / (R2² + (s·X2)²)— Rotor-side form (stator impedance neglected).s_m = R2' / √(R1² + X²) ≈ R2' / X— Slip at maximum torque.Tmax = 3·V1² / (2·ωs·X)— Maximum torque (R1 neglected); independent of R2.T / Tmax = 2·s·s_m / (s² + s_m²) ; Tst / Tmax = 2·s_m / (1 + s_m²)— Kloss relations (R1 neglected).T ∝ V1²at a given slip.
Starting and Speed Control of Induction Motors
Tst / Tfl = (Ist / Ifl)²·sfl— Starting-to-full-load torque ratio.Star–delta: I_line and Tst = 1/3 of DOL values.Autotransformer (tap x): I_motor = x·Isc ; I_line = x²·Isc ; Tst = x²·Tst,DOL.N = (120·f / P)·(1 − s)— Speed; control via f (with V/f constant), P (pole changing) or s (rotor resistance, voltage).Low slip, constant torque: s ∝ R2 ; s ∝ 1/V².
Single-phase Induction Motors
s_f = s ; s_b = 2 − s— Slip with respect to forward and backward fields.f_rotor,b = (2 − s)·f— Rotor frequency due to the backward field (Hz).T = (Pf − Pb) / ωs— Net torque from forward and backward air-gap powers (N·m).
Stepper Motors and Servo Motors
θs = 360° / (m·Nr) = 360°·(Ns − Nr) / (Ns·Nr)— VR stepper step angle; m phases, Nr rotor teeth, Ns stator teeth.θs = 360° / (2·m·Nr)— Hybrid stepper full-step angle (e.g. 2 phases, 50 teeth → 1.8°).N = 60·f·θs / 360°— Speed (rpm) at pulse rate f (pulses/s).ω(s)/Va(s) = K / (1 + τm·s) ; K = Kt/(Ra·B + Kt·Kb) ; τm = Ra·J/(Ra·B + Kt·Kb)— Armature-controlled DC servo (La neglected).
Synchronous Machines: Basic Principle and Applications
Ns = 120·f / P— Synchronous speed (rpm).Eph = 4.44·f·Φ·Tph·kw— EMF per phase (V); Tph turns per phase, kw winding factor.E = V + I·(Ra + j·Xs)— Generator phasor equation per phase (motor: V = E + I·(Ra + j·Xs)).P = 3·V·E·sin δ / Xs ; Pmax = 3·V·E / Xs— Power–angle relation (W), Ra neglected; δ load angle.