Process Instrumentation and Control — formula sheet

Chemical Engineering · GATE CH · SI units. Drafted with Aria, checked by the AiCanCode.org team.

Measurement of temperature, pressure, flow and level

  • I = 4 + 16·(x − LRV)/(URV − LRV) — linear 4–20 mA transmitter; I current (mA), x measured value, LRV/URV lower and upper range values; span = URV − LRV.
  • R_T = R₀·(1 + α·T) — RTD; R₀ resistance at 0 °C (Ω), α ≈ 0.00385 /°C for platinum, T (°C).
  • ΔP = (ρ_m − ρ)·g·h_m — differential manometer; ρ_m manometer fluid, ρ flowing fluid (kg/m³), g = 9.81 m/s², h_m reading (m), ΔP (Pa).
  • Q = C_d·A₀·√(2·ΔP/(ρ·(1 − β⁴))) — orifice/venturi; Q (m³/s), C_d discharge coefficient (≈0.61 orifice, ≈0.98 venturi), A₀ throat area (m²), β = d₀/D; incompressible flow.
  • Q₂/Q₁ = √(ΔP₂/ΔP₁) — head meters: flow varies as the square root of differential pressure.
  • ΔP = ρ·g·h — hydrostatic level; h liquid height above the lower tap (m).

Composition analysers and transmitters

  • A = −log₁₀(I/I₀) = ε·b·c — Beer–Lambert law; A absorbance, ε molar absorptivity (m²/mol), b path length (m), c concentration (mol/m³); dilute samples.
  • θ_line = V_line/Q_sample — sample-line transport delay (s); V (m³), Q (m³/s).
  • θ ≈ θ_line + 1.5·T_cycle — approximate dead time of a sampled analyser (GC) with cycle time T_cycle (s).
  • E = s·(7 − pH), s = 2.303·R·T/F — ideal glass electrode; s = 59.16 mV/pH at 298.15 K, T (K).

Laplace transforms for process dynamics

  • F(s) = ∫₀^∞ f(t)·e^(−s·t) dt — definition; s (1/s).
  • L{1} = 1/s, L{t} = 1/s², L{δ(t)} = 1 — step, ramp, impulse.
  • L{e^(−a·t)} = 1/(s + a), L{t·e^(−a·t)} = 1/(s + a)² — exponentials.
  • L{sin ω·t} = ω/(s² + ω²), L{e^(−a·t)·sin ω·t} = ω/((s + a)² + ω²) — sinusoids.
  • L{df/dt} = s·F(s) − f(0) — derivative; f(0) = 0 for deviation variables.
  • L{f(t − θ)} = e^(−θ·s)·F(s) — dead time θ (s).
  • lim(t→∞) f(t) = lim(s→0) s·F(s) — final-value theorem; valid only if s·F(s) has all poles in the left half-plane.
  • lim(t→0⁺) f(t) = lim(s→∞) s·F(s) — initial-value theorem.

First-order systems and their dynamic response

  • G(s) = K/(τ·s + 1) — first-order system; K steady-state gain, τ time constant (s).
  • y(t) = K·M·(1 − e^(−t/τ)) — response to a step of size M; 63.2 % at t = τ, 95 % at 3τ.
  • y(t) = K·a·(t − τ + τ·e^(−t/τ)) — response to a ramp of slope a; long-time lag a·τ (K = 1).
  • AR = K/√(1 + ω²·τ²), φ = −tan⁻¹(ω·τ) — sinusoidal response; ω (rad/s).
  • τ = m·Cp/(h·A), τ = A·R (K = R), τ = V/q — thermometer, linear tank, stirred mixing tank.

First-order systems in series and interacting systems

  • G(s) = K₁·K₂/((τ₁·s + 1)·(τ₂·s + 1)) — non-interacting lags in series.
  • y(t) = K·M·[1 − (τ₁·e^(−t/τ₁) − τ₂·e^(−t/τ₂))/(τ₁ − τ₂)] — step response of two unequal lags.
  • y(t) = K·M·[1 − (1 + t/τ)·e^(−t/τ)] — two equal lags.
  • Q₂/Q = 1/(τ₁·τ₂·s² + (τ₁ + τ₂ + A₁·R₂)·s + 1) — two interacting tanks; τ₁ = A₁R₁, τ₂ = A₂R₂; always overdamped.

Second-order systems: underdamped and overdamped response

  • G(s) = K/(τ²·s² + 2·ζ·τ·s + 1) — τ natural period (s), ζ damping factor; ω_n = 1/τ.
  • OS = exp(−π·ζ/√(1 − ζ²)) — overshoot (0 < ζ < 1).
  • DR = OS² — decay ratio.
  • T = 2·π·τ/√(1 − ζ²), t_p = π·τ/√(1 − ζ²) — period of oscillation and time to first peak.
  • t_s ≈ 4·τ/ζ — settling time to ±2 %.
  • ζ = −ln(OS)/√(π² + (ln OS)²) — damping factor from measured overshoot.
  • τ₁, τ₂ = τ/(ζ ∓ √(ζ² − 1)) — time constants of an overdamped system (ζ > 1).

Transportation lag and linearisation

  • θ = L/v = V/q — plug-flow dead time (s); L (m), v (m/s), V (m³), q (m³/s).
  • e^(−θ·s) ≈ (1 − θ·s/2)/(1 + θ·s/2) — first-order Padé approximation.
  • AR = 1, φ = −ω·θ (rad) — frequency response of dead time.
  • f(x) ≈ f(x_s) + (df/dx)_s·(x − x_s) — Taylor linearisation about steady state x_s.
  • R = 2·√h_s/C = 2·h_s/q_s — linearised resistance of a tank with q = C·√h; τ = A·R.

Block diagrams and closed-loop transfer functions

  • G_OL = G_c·G_v·G_p·G_m — open-loop transfer function (product of all blocks around the loop).
  • C/R = G_c·G_v·G_p/(1 + G_OL) — servo response (unity set-point gain).
  • C/L = G_d/(1 + G_OL) — regulator (load) response.
  • 1 + G_OL(s) = 0 — characteristic equation.
  • G/(1 + G·H) — negative-feedback loop reduction; G forward path, H feedback path.

Proportional, integral and derivative control actions

  • p(t) = p̄ + K_c·[e + (1/τ_I)·∫e dt + τ_D·de/dt] — ideal PID; p̄ bias, e = set point − measurement, τ_I and τ_D (s).
  • G_c(s) = K_c·(1 + 1/(τ_I·s) + τ_D·s) — PID transfer function.
  • PB = 100/K_c — proportional band (%), K_c dimensionless.
  • Δp = K_c·E·(1 + t/τ_I) — PI output for a constant error step E.
  • Offset = 1/(1 + K_c·K_p) — P control, unit set-point step, self-regulating process.

Control valves: characteristics and sizing

  • q = C_v·f(x)·√(ΔP/SG) — liquid valve; q (US gpm), ΔP (psi), SG specific gravity, f(x) fractional flow at lift x.
  • q = K_v·f(x)·√(ΔP/SG) — SI form; q (m³/h), ΔP (bar); C_v = 1.156·K_v.
  • f = x, f = R^(x − 1), f ≈ √x — linear, equal-percentage (rangeability R) and quick-opening characteristics.
  • q = K_v·f·√ΔP_T/√(1 + k·K_v²·f²) — installed flow (water) with fixed total drop ΔP_T (bar) and line loss k·q².

Closed-loop response to servo and regulator problems

  • τ_CL = τ/(1 + K), K = K_c·K_p — P control of a first-order process.
  • Offset = 1/(1 + K), load effect = K_d/(1 + K) — P control, unit set-point and unit load steps.
  • τ_I·τ·s² + τ_I·(1 + K)·s + K = 0 — characteristic equation, PI control of a first-order process; no offset.
  • ζ = ((1 + K)/2)·√(τ_I/(K·τ)) — closed-loop damping under PI control.

Routh stability criterion and root locus

  • a₀·sⁿ + a₁·sⁿ⁻¹ + … + aₙ = 0 — characteristic polynomial; all coefficients positive is necessary for stability.
  • b₁ = (a₁·a₂ − a₀·a₃)/a₁ — Routh array element; sign changes in the first column = number of right-half-plane roots.
  • a₁·a₂ > a₀·a₃ — stability condition for a cubic (all aᵢ > 0).
  • ω_u = √(a₃/a₁), P_u = 2·π/ω_u — oscillation frequency and period at the ultimate gain (cubic).
  • σ = (Σp − Σz)/(n − m), θ_q = (2q + 1)·180°/(n − m) — root-locus centroid and asymptote angles.

Frequency response: Bode plots

  • AR = |G(j·ω)|, φ = ∠G(j·ω) — substitution rule; ω (rad/s).
  • AR_dB = 20·log₁₀ AR — decibels.
  • ω_c = 1/τ — corner frequency of a first-order lag; AR = 0.707, φ = −45° there.
  • AR = 1/√((1 − ω²τ²)² + (2ζωτ)²) — second-order lag.
  • AR = AR₁·AR₂·…, φ = φ₁ + φ₂ + … — elements in series.

Bode and Nyquist stability criteria, gain and phase margins

  • φ_OL(ω_co) = −180° — phase-crossover frequency; closed loop stable if AR_OL(ω_co) < 1.
  • GM = 1/AR_OL(ω_co) — gain margin (typically 1.7–2).
  • PM = 180° + φ_OL(ω_g), AR_OL(ω_g) = 1 — phase margin (typically 30–45°).
  • K_cu = 1/AR_p(ω_co), P_u = 2·π/ω_co — ultimate gain and period.
  • Z = N + P — Nyquist: unstable closed-loop poles = clockwise encirclements of (−1, 0) + open-loop RHP poles.

Controller tuning: Ziegler-Nichols and Cohen-Coon

  • K_c = 0.5·K_cu — Ziegler–Nichols P.
  • K_c = 0.45·K_cu, τ_I = P_u/1.2 — Ziegler–Nichols PI.
  • K_c = 0.6·K_cu, τ_I = P_u/2, τ_D = P_u/8 — Ziegler–Nichols PID.
  • τ = 1.5·(t₆₃ − t₂₈), θ = t₆₃ − τ, K = Δy_∞/M — FOPDT fit from a process reaction curve.
  • K_c = 1.2·τ/(K·θ), τ_I = 2·θ, τ_D = 0.5·θ — Ziegler–Nichols open-loop PID.
  • K_c = (1/K)·(τ/θ)·(0.9 + θ/(12·τ)), τ_I = θ·(30 + 3·θ/τ)/(9 + 20·θ/τ) — Cohen–Coon PI.
  • K_c = (1/K)·(τ/θ)·(4/3 + θ/(4·τ)), τ_I = θ·(32 + 6·θ/τ)/(13 + 8·θ/τ), τ_D = 4·θ/(11 + 2·θ/τ) — Cohen–Coon PID.

Cascade, feedforward and ratio control

  • G_f = −G_d/G_p — ideal feedforward controller; static form G_f = −K_d/K_p.
  • G_f = −(K_d/K_p)·(τ_p·s + 1)/(τ_d·s + 1)·e^(−(θ_d − θ_p)·s) — FOPDT paths; realisable if θ_d ≥ θ_p.
  • G_inner = G_c2·G_p2/(1 + G_c2·G_p2·G_m2) — closed inner loop of a cascade.
  • F_c,sp = R·F_w — ratio control set point; F_w wild-stream flow, R desired ratio.

Control of distillation columns, heat exchangers and reactors

  • R = L/D — reflux ratio; L reflux, D distillate (mol/s).
  • λ₁₁ = 1/(1 − K₁₂·K₂₁/(K₁₁·K₂₂)) — relative gain of a 2 × 2 system; pair on λ close to 1, never on negative λ.
  • K_s = λ/(m·Cp) — gain of steam-heater outlet temperature to steam flow (K per kg/s); λ latent heat (J/kg).
  • dQ_rem/dT > dQ_gen/dT — open-loop stability of an exothermic CSTR steady state.

Introduction to DCS, PLC and P&ID symbols

  • V = I·R — 250 Ω input resistor turns 4–20 mA into 1–5 V.
  • Counts = (V/V_FS)·(2ⁿ − 1) — n-bit A/D converter reading.
  • Δp_k = K_c·[(e_k − e_(k−1)) + (Δt/τ_I)·e_k + (τ_D/Δt)·(e_k − 2·e_(k−1) + e_(k−2))] — velocity-form digital PID; Δt sampling interval (s).
  • t_response ≈ 2·t_scan — worst-case PLC response to an input change.