Process Instrumentation and Control — formula sheet
Chemical Engineering · GATE CH · SI units. Drafted with Aria, checked by the AiCanCode.org team.
Measurement of temperature, pressure, flow and level
I = 4 + 16·(x − LRV)/(URV − LRV)— linear 4–20 mA transmitter; I current (mA), x measured value, LRV/URV lower and upper range values; span = URV − LRV.R_T = R₀·(1 + α·T)— RTD; R₀ resistance at 0 °C (Ω), α ≈ 0.00385 /°C for platinum, T (°C).ΔP = (ρ_m − ρ)·g·h_m— differential manometer; ρ_m manometer fluid, ρ flowing fluid (kg/m³), g = 9.81 m/s², h_m reading (m), ΔP (Pa).Q = C_d·A₀·√(2·ΔP/(ρ·(1 − β⁴)))— orifice/venturi; Q (m³/s), C_d discharge coefficient (≈0.61 orifice, ≈0.98 venturi), A₀ throat area (m²), β = d₀/D; incompressible flow.Q₂/Q₁ = √(ΔP₂/ΔP₁)— head meters: flow varies as the square root of differential pressure.ΔP = ρ·g·h— hydrostatic level; h liquid height above the lower tap (m).
Composition analysers and transmitters
A = −log₁₀(I/I₀) = ε·b·c— Beer–Lambert law; A absorbance, ε molar absorptivity (m²/mol), b path length (m), c concentration (mol/m³); dilute samples.θ_line = V_line/Q_sample— sample-line transport delay (s); V (m³), Q (m³/s).θ ≈ θ_line + 1.5·T_cycle— approximate dead time of a sampled analyser (GC) with cycle time T_cycle (s).E = s·(7 − pH),s = 2.303·R·T/F— ideal glass electrode; s = 59.16 mV/pH at 298.15 K, T (K).
Laplace transforms for process dynamics
F(s) = ∫₀^∞ f(t)·e^(−s·t) dt— definition; s (1/s).L{1} = 1/s,L{t} = 1/s²,L{δ(t)} = 1— step, ramp, impulse.L{e^(−a·t)} = 1/(s + a),L{t·e^(−a·t)} = 1/(s + a)²— exponentials.L{sin ω·t} = ω/(s² + ω²),L{e^(−a·t)·sin ω·t} = ω/((s + a)² + ω²)— sinusoids.L{df/dt} = s·F(s) − f(0)— derivative; f(0) = 0 for deviation variables.L{f(t − θ)} = e^(−θ·s)·F(s)— dead time θ (s).lim(t→∞) f(t) = lim(s→0) s·F(s)— final-value theorem; valid only if s·F(s) has all poles in the left half-plane.lim(t→0⁺) f(t) = lim(s→∞) s·F(s)— initial-value theorem.
First-order systems and their dynamic response
G(s) = K/(τ·s + 1)— first-order system; K steady-state gain, τ time constant (s).y(t) = K·M·(1 − e^(−t/τ))— response to a step of size M; 63.2 % at t = τ, 95 % at 3τ.y(t) = K·a·(t − τ + τ·e^(−t/τ))— response to a ramp of slope a; long-time lag a·τ (K = 1).AR = K/√(1 + ω²·τ²),φ = −tan⁻¹(ω·τ)— sinusoidal response; ω (rad/s).τ = m·Cp/(h·A),τ = A·R(K = R),τ = V/q— thermometer, linear tank, stirred mixing tank.
First-order systems in series and interacting systems
G(s) = K₁·K₂/((τ₁·s + 1)·(τ₂·s + 1))— non-interacting lags in series.y(t) = K·M·[1 − (τ₁·e^(−t/τ₁) − τ₂·e^(−t/τ₂))/(τ₁ − τ₂)]— step response of two unequal lags.y(t) = K·M·[1 − (1 + t/τ)·e^(−t/τ)]— two equal lags.Q₂/Q = 1/(τ₁·τ₂·s² + (τ₁ + τ₂ + A₁·R₂)·s + 1)— two interacting tanks; τ₁ = A₁R₁, τ₂ = A₂R₂; always overdamped.
Second-order systems: underdamped and overdamped response
G(s) = K/(τ²·s² + 2·ζ·τ·s + 1)— τ natural period (s), ζ damping factor; ω_n = 1/τ.OS = exp(−π·ζ/√(1 − ζ²))— overshoot (0 < ζ < 1).DR = OS²— decay ratio.T = 2·π·τ/√(1 − ζ²),t_p = π·τ/√(1 − ζ²)— period of oscillation and time to first peak.t_s ≈ 4·τ/ζ— settling time to ±2 %.ζ = −ln(OS)/√(π² + (ln OS)²)— damping factor from measured overshoot.τ₁, τ₂ = τ/(ζ ∓ √(ζ² − 1))— time constants of an overdamped system (ζ > 1).
Transportation lag and linearisation
θ = L/v = V/q— plug-flow dead time (s); L (m), v (m/s), V (m³), q (m³/s).e^(−θ·s) ≈ (1 − θ·s/2)/(1 + θ·s/2)— first-order Padé approximation.AR = 1,φ = −ω·θ(rad) — frequency response of dead time.f(x) ≈ f(x_s) + (df/dx)_s·(x − x_s)— Taylor linearisation about steady state x_s.R = 2·√h_s/C = 2·h_s/q_s— linearised resistance of a tank with q = C·√h; τ = A·R.
Block diagrams and closed-loop transfer functions
G_OL = G_c·G_v·G_p·G_m— open-loop transfer function (product of all blocks around the loop).C/R = G_c·G_v·G_p/(1 + G_OL)— servo response (unity set-point gain).C/L = G_d/(1 + G_OL)— regulator (load) response.1 + G_OL(s) = 0— characteristic equation.G/(1 + G·H)— negative-feedback loop reduction; G forward path, H feedback path.
Proportional, integral and derivative control actions
p(t) = p̄ + K_c·[e + (1/τ_I)·∫e dt + τ_D·de/dt]— ideal PID; p̄ bias, e = set point − measurement, τ_I and τ_D (s).G_c(s) = K_c·(1 + 1/(τ_I·s) + τ_D·s)— PID transfer function.PB = 100/K_c— proportional band (%), K_c dimensionless.Δp = K_c·E·(1 + t/τ_I)— PI output for a constant error step E.Offset = 1/(1 + K_c·K_p)— P control, unit set-point step, self-regulating process.
Control valves: characteristics and sizing
q = C_v·f(x)·√(ΔP/SG)— liquid valve; q (US gpm), ΔP (psi), SG specific gravity, f(x) fractional flow at lift x.q = K_v·f(x)·√(ΔP/SG)— SI form; q (m³/h), ΔP (bar); C_v = 1.156·K_v.f = x,f = R^(x − 1),f ≈ √x— linear, equal-percentage (rangeability R) and quick-opening characteristics.q = K_v·f·√ΔP_T/√(1 + k·K_v²·f²)— installed flow (water) with fixed total drop ΔP_T (bar) and line loss k·q².
Closed-loop response to servo and regulator problems
τ_CL = τ/(1 + K),K = K_c·K_p— P control of a first-order process.Offset = 1/(1 + K),load effect = K_d/(1 + K)— P control, unit set-point and unit load steps.τ_I·τ·s² + τ_I·(1 + K)·s + K = 0— characteristic equation, PI control of a first-order process; no offset.ζ = ((1 + K)/2)·√(τ_I/(K·τ))— closed-loop damping under PI control.
Routh stability criterion and root locus
a₀·sⁿ + a₁·sⁿ⁻¹ + … + aₙ = 0— characteristic polynomial; all coefficients positive is necessary for stability.b₁ = (a₁·a₂ − a₀·a₃)/a₁— Routh array element; sign changes in the first column = number of right-half-plane roots.a₁·a₂ > a₀·a₃— stability condition for a cubic (all aᵢ > 0).ω_u = √(a₃/a₁),P_u = 2·π/ω_u— oscillation frequency and period at the ultimate gain (cubic).σ = (Σp − Σz)/(n − m),θ_q = (2q + 1)·180°/(n − m)— root-locus centroid and asymptote angles.
Frequency response: Bode plots
AR = |G(j·ω)|,φ = ∠G(j·ω)— substitution rule; ω (rad/s).AR_dB = 20·log₁₀ AR— decibels.ω_c = 1/τ— corner frequency of a first-order lag; AR = 0.707, φ = −45° there.AR = 1/√((1 − ω²τ²)² + (2ζωτ)²)— second-order lag.AR = AR₁·AR₂·…,φ = φ₁ + φ₂ + …— elements in series.
Bode and Nyquist stability criteria, gain and phase margins
φ_OL(ω_co) = −180°— phase-crossover frequency; closed loop stable if AR_OL(ω_co) < 1.GM = 1/AR_OL(ω_co)— gain margin (typically 1.7–2).PM = 180° + φ_OL(ω_g),AR_OL(ω_g) = 1— phase margin (typically 30–45°).K_cu = 1/AR_p(ω_co),P_u = 2·π/ω_co— ultimate gain and period.Z = N + P— Nyquist: unstable closed-loop poles = clockwise encirclements of (−1, 0) + open-loop RHP poles.
Controller tuning: Ziegler-Nichols and Cohen-Coon
K_c = 0.5·K_cu— Ziegler–Nichols P.K_c = 0.45·K_cu,τ_I = P_u/1.2— Ziegler–Nichols PI.K_c = 0.6·K_cu,τ_I = P_u/2,τ_D = P_u/8— Ziegler–Nichols PID.τ = 1.5·(t₆₃ − t₂₈),θ = t₆₃ − τ,K = Δy_∞/M— FOPDT fit from a process reaction curve.K_c = 1.2·τ/(K·θ),τ_I = 2·θ,τ_D = 0.5·θ— Ziegler–Nichols open-loop PID.K_c = (1/K)·(τ/θ)·(0.9 + θ/(12·τ)),τ_I = θ·(30 + 3·θ/τ)/(9 + 20·θ/τ)— Cohen–Coon PI.K_c = (1/K)·(τ/θ)·(4/3 + θ/(4·τ)),τ_I = θ·(32 + 6·θ/τ)/(13 + 8·θ/τ),τ_D = 4·θ/(11 + 2·θ/τ)— Cohen–Coon PID.
Cascade, feedforward and ratio control
G_f = −G_d/G_p— ideal feedforward controller; static form G_f = −K_d/K_p.G_f = −(K_d/K_p)·(τ_p·s + 1)/(τ_d·s + 1)·e^(−(θ_d − θ_p)·s)— FOPDT paths; realisable if θ_d ≥ θ_p.G_inner = G_c2·G_p2/(1 + G_c2·G_p2·G_m2)— closed inner loop of a cascade.F_c,sp = R·F_w— ratio control set point; F_w wild-stream flow, R desired ratio.
Control of distillation columns, heat exchangers and reactors
R = L/D— reflux ratio; L reflux, D distillate (mol/s).λ₁₁ = 1/(1 − K₁₂·K₂₁/(K₁₁·K₂₂))— relative gain of a 2 × 2 system; pair on λ close to 1, never on negative λ.K_s = λ/(m·Cp)— gain of steam-heater outlet temperature to steam flow (K per kg/s); λ latent heat (J/kg).dQ_rem/dT > dQ_gen/dT— open-loop stability of an exothermic CSTR steady state.
Introduction to DCS, PLC and P&ID symbols
V = I·R— 250 Ω input resistor turns 4–20 mA into 1–5 V.Counts = (V/V_FS)·(2ⁿ − 1)— n-bit A/D converter reading.Δp_k = K_c·[(e_k − e_(k−1)) + (Δt/τ_I)·e_k + (τ_D/Δt)·(e_k − 2·e_(k−1) + e_(k−2))]— velocity-form digital PID; Δt sampling interval (s).t_response ≈ 2·t_scan— worst-case PLC response to an input change.